EasyManua.ls Logo

Trane Voyager CV - Installation Electrical; Electrical Service Sizing Data (60 Hz)

Trane Voyager CV
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation Electrical
RT-SVX34F-EN 25
Table 7. 27½-50 ton electrical service sizing data—60Hz
1
Fan Motors
Model
Electrical
Characteristics
Allowable
Voltage
Range
Compressor Supply Condenser Exhaust
No/Ton RLA (Ea.) LRA (Ea.) HP FLA No HP
FLA
(Ea.)
50% 100%
HP
FLA
(Ea.)No.
TC/TE/
YC*330
208/60/3 187-229
1/12,1/
13
44.0/50.5 304/315
7.5
10.0
22.2
29.5
3 1.1 7.0 1 2 1.0 4.1
230/60/3 207-253
1/12,1/
13
44.0/50.5 304/315
7.5
10.0
18.8
25.2
3 1.1 7.0 1 2 1.0 4.1
460/60/3 414-506
1/12,1/
13
21.0/23.0 147/158
7.5
10.0
9.4
12.6
3 1.1 3.5 1 2 1.0 1.8
575/60/3 517-633
1/12,1/
13
17.5/19.0 122/136
7.5
10.0
7.8
10.1
3 1.1 2.8 1 2 1.0 1.4
TC/TE/
YC*360
208/60/3 187-229 2/13 50.5 315/315
7.5
10.0
22.2
29.5
3 1.1 7.0 1 2 1.0 4.1
230/60/3 207-253 2/13 50.5 315/315
7.5
10.0
18.8
25.2
3 1.1 7.0 1 2 1.0 4.1
460/60/3 414-506 2/13 23.0 158/158
7.5
10.0
9.4
12.6
3 1.1 3.5 1 2 1.0 1.8
575/60/3 517-633 2/13 19.0 136/136
7.5
10.0
7.8
10.1
3 1.1 2.8 1 2 1.0 1.4
TC/TE/
YC*420
208/60/3 187-229
1/13,1/
15
50.5/56.0 315/351
7.5
10.0
15.0
22.2
29.5
40.7
3 1.1 7.0 1 2 1.0 4.1
230/60/3 207-253
1/13,1/
15
50.5/56.0 315/351
7.5
10.0
15.0
18.8
25.2
35.4
3 1.1 7.0 1 2 1.0 4.1
460/60/3 414-506
1/13,1/
15
23.0/27.5 158/197
7.5
10.0
15.0
9.4
12.6
17.7
3 1.1 3.5 1 2 1.0 1.8
575/60/3 517-633
1/13,1/
15
19.0/23.0 136/146
7.5
10.0
15.0
7.8
10.1
15.1
3 1.1 2.8 1 2 1.0 1.4
TC/TE/
YC*480
208/60/3 187-229
1/13,1/
20
50.5/83.9 315/485
10.0
15.0
29.5
40.7
4 1.1 7.0 1 2 1.5 5.4
230/60/3 207-253
1/13,1/
20
50.5/83.9 315/485
10.0
15.0
25.2
35.4
4 1.1 7.0 1 2 1.5 5.4
460/60/3 414-506
1/13,1/
20
23.0/34.0 158/215
10.0
15.0
12.6
17.7
4 1.1 3.5 1 2 1.5 2.7
575/60/3 517-633
1/13,1/
20
19.0/27.3 136/175
10.0
15.0
10.1
15.1
4 1.1 2.8 1 2 1.5 2.2
TC/TE/
YC*600
208/60/3 187-229
2/13,1/
15
50.5/56.0 315/351
10.0
15.0
20.0
29.5
40.7
56.1
4 1.1 7.0 1 2 1.5 5.4
230/60/3 207-253
2/13,1/
15
50.5/56.0 315/351
10.0
15.0
20.0
25.2
35.4
49.4
4 1.1 7.0 1 2 1.5 5.4
460/60/3 414-506
2/13,1/
15
23.0/27.5 158/197
10.0
15.0
20.0
12.6
17.7
24.7
4 1.1 3.5 1 2 1.5 2.7
575/60/3 517-633
2/13,1/
15
19.0/23.0 136/146
10.0
15.0
20.0
10.1
15.1
19.6
4 1.1 2.8 1 2 1.5 2.2
Notes:
1. All customer wiring and devices must be installed in accordance with local and national electrical codes.
2. 100% Power Exhaust is with or without Statitrac™.

Table of Contents

Related product manuals