Table 8. Electrical service sizing data — electric heat
module (electric heat only) — 60 Hz
Models: TE(D,H,F,R) 330—600 Electric Heat FLA
KW Heater
Nominal
Unit Size
(Tons)
Nominal
Unit
Voltage
36 54 72 90 108
FLA FLA FLA FLA FLA
27½-35
208 74.9 112.4 — — —
230 86.6 129.9 — — —
460 43.3 65.0 86.6 108.3 —
575 — 52.0 69.3 86.6 —
40- 50
208 — 112.4 — — —
230 — 129.9 — — —
460 — 65.0 86.6 108.3 129.9
575 — 52.0 69.3 86.6 103.9
Note: All FLA in this table are based on heater operating at 208, 240, 480,
and 600 volts.
Table 9. Electrical service sizing data — crankcase
heaters (heating mode only) — 60Hz
Nominal
Unit Size (Tons)
FLA Add Unit Voltage
200 230 460 575
27½ - 35 1111
40, 50 2211
Table 10. Electrical service sizing data — 50Hz
Model
Electrical
Characteristics
Compressor
Fan Motors
Supply Condenser
1
Exhaust
No/Ton
RLA
(Ea.)
LRA
(Ea.) HP(kW) FLA No. HP(kW)
FLA
(Ea.)
50% 100%
4
HP
(kW)
FLA
(Ea.)No.
TC/TE/YC*275 380-415/50/3 1/10, 1/11 21.0/23.0 147/ 158 7.5 (5.6)
13.6/
14.1
3 .75 (.56) 4.4 1 2
0.75
(0.56)
1.7
10 (6.8)
16.0/
15.5
TC/TE/YC*305 380-415/50/3 2/11 23.0 158 7.5 (5.6)
13.6/
14.1
3
0.75
(0.56)
4.4 1 2
0.75
(0.56)
1.7
10 (6.8)
16.0/
15.5
TC/TE/YC*350 380-415/50/3 1/11, 1/12 23.0/27.5 158/ 197 7.5 (5.6)
13.6/
14.1
3
0.75
(0.56)
4.4 1 2
0.75
(0.56)
1.7
10 (6.8)
16.0/
15.5
15 (10.5)
24.0/
26.0
TC/TE/YC*400 380-415/50/3 1/11, 1/17 23.0/34.0 158/ 215 10 (6.8)
16.0/
15.5
4
0.75
(0.56)
4.4 1 2
1.0
(0.75)
2.5
15 (10.5)
24.0/
26.0
TC/TE/YC*500 380-415/50/3 2/11, 1/12 23.0/27.5 158/ 197 10 (6.8)
16.0/
15.5
4
0.75
(0.56)
4.4 1 2
1.0
(0.75)
2.5
15 (10.5)
24.0/
26.0
20 (12.8)
29.0/
28.0
Notes:
1. All condenser fan motors are single phase.
2. All customer wiring and devices must be installed in accordance with local and national electrical codes.
3. Allowable voltage range for the 380V unit is 342-418V, allowable voltage range for the 415V unit is 373-456.
4. 100% Power Exhaust is with or without Statitrac.