Installation
22 RT-SVX25G-EN
2. Ensure that the AC control wiring between the controls
and the unit’s termination point does not exceed three
(3) ohms/conductor for the length of the run.
Note: Resistance in excess of 3 ohms per conductor
could cause component failure due to insufficient
AC voltage supply.
3. Be sure to check all loads and conductors for grounds,
shorts, and mis-wiring.
4. Do not run the AC low voltage wiring in the same
conduit with the high voltage power wiring.
5. Route low voltage wiring per illustrations on
the next
page.
Controls using DC Analog Input/Outputs
(Standard Low Voltage Multiconductor
Wire)
Before installing any connecting wiring between the unit
and components utilizing a DC analog input\output signal,
refer to “Unit Dimensions,” p. 12 for the electrical access
locations provided on the unit.
1.
Table 4 lists the conductor sizing guidelines that must
be followed when interconnecting the DC binary
output devices and the system components utilizing a
DC analog input\output signal to the unit.
Note: Resistance in excess of 2.5 ohms per conductor can
cause deviations in the accuracy of the controls.
2. Ensure that the wiring between controls and the unit’s
termination point does not exceed two and a half (2.5)
ohms/conductor for the length of the run.
3. Do not run the electrical wires transporting DC signals
in or around conduit housing high voltage wires
Table 3. Electromechanical thermostat 24 Vac
conductors with ReliaTel™
Di st a n ce f r o m Un it t o
Co n t r ol Re com m e n d ed W i r e Si z e
000460 feet 18 gauge
000140 m 0.75 m m
2
461732 feet 16 gauge
Table 4. Zone sensor module wiring
Di st a n ce f r o m U n it t o
Co n t r o l Reco m m e n d ed W ir e Si ze
0150 feet ( 045.7 m ) 22 gauge (0.33 m m
2
)
151 240 feet (4673.1 m ) 20 gauge ( 0.50 m m
2
)
241385 feet ( 73.5117.3 m ) 18 gauge ( 0.75 m m
2
)
386610 feet ( 117.7185.9 m ) 16 gauge ( 1.3 m m
2
)
611970 feet ( 186.2295.7 m ) 14 gauge ( 2.0 m m
2
)
Figure 14. ReliaTel™ options module
Figure 15. ReliaTel conventional thermostat field wiring
diagram
RTRM