18 RT-SVX23F-EN
Installation
WARNING
Heavy Objects!
Ensure that all the lifting equipment used is properly
rated for the weight of the unit being lifted. Each of the
cables (chains or slings), hooks, and shackles used to
lift the unit must be capable of supporting the entire
weight of the unit. Lifting cables (chains or slings) may
not be of the same length. Adjust as necessary for even
unit lift. Other lifting arrangements could cause
equipment or property damage. Failure to follow
instructions above or properly lift unit could result in
unit dropping and possibly crushing operator/
technician which could result in death or serious injury.
WARNING
Improper Unit Lift!
Test lift unit approximately 24 inches to verify proper
center of gravity lift point. To avoid dropping of unit,
reposition lifting point if unit is not level. Failure to
properly lift unit could result in unit dropping and
possibly crushing operator/technician which could
result in death or serious injury and possible equipment
or property-only damage.
Table 1. Maximum unit & corner weights (lbs) and center of gravity dimensions (in.)
Unit
Maximum Model
Weights
(a)
Corner Weights
(b)
Center of Gravity (in.)
Tons Model No. Shipping Net A B C D Length Width
3 WSC036E 589 514 177 107 113 117 29 20
4 WSC048E 600 525 181 109 115 119 29 20
5 WSC060E 825 682 228 177 114 163 38 24
6 WSC072E 835 740 235 196 140 168 40 22
WSC090E 902 804 255 217 153 180 41 22
10 WSC120E 1431 1219 355 333 257 274 48 28
(a)Weights are approximate.
(b)Corner weights are given for information only.
Figure 12. Corner weights Figure 13. Rigging and center-of-gravity data