EasyManua.ls Logo

Trane WSC060-120 - Net Heating Capacities Tables (SI); Net Heating Capacities Tables (IP)

Trane WSC060-120
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
18
PKGP-PRC004-EN
Performance
Data
Table PD-5 – Net Heating Capacities (kW) WSC060AD,T at 3,400 m
3
/h (SI)
Integrated Heating Capacity (kW) Total Power (kW)
Outdoor At Indicated Indoor Dry Bulb Temp (C) At Indicated Indoor Dry Bulb Temp (C)
Temp (C) 15 21 24 27 15 21 24 27
–24 4.1 4.1 4.1 4.0 3.2 3.7 3.9 4.2
–21 4.9 4.9 4.8 4.8 3.3 3.8 4.0 4.3
–18 5.8 5.7 5.6 5.5 3.4 3.8 4.1 4.3
–15 6.7 6.5 6.4 6.3 3.5 3.9 4.2 4.4
–12 7.6 7.4 7.3 7.2 3.6 4.0 4.3 4.5
–9 8.6 8.3 8.2 8.1 3.7 4.1 4.3 4.6
–6 9.6 9.3 9.1 9.0 3.8 4.2 4.4 4.7
–3 10.6 10.3 10.1 10.0 3.9 4.3 4.5 4.8
0 11.7 11.4 11.2 11.0 4.0 4.4 4.6 4.9
3 12.8 12.4 12.2 12.0 4.1 4.5 4.7 5.0
6 13.9 13.5 13.3 13.1 4.2 4.6 4.8 5.1
9 16.7 16.2 15.9 15.7 4.3 4.7 5.0 5.2
12 18.0 17.4 17.1 16.9 4.4 4.8 5.1 5.4
15 19.3 18.7 18.4 18.1 4.5 5.0 5.2 5.5
18 20.7 20.1 19.7 19.4 4.7 5.2 5.4 5.7
21 22.1 21.4 21.1 20.7 4.8 5.3 5.6 5.9
24 23.6 22.8 22.4 22.1 5.0 5.5 5.8 6.1
Notes:
1. Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand
defrost cycle.
Table PD-5a — Net Heating Capacities (MBH) WSC060AD,T at 2,000 CFM (IP)
Integrated Heating Capacity (MBh) Total Power (kW)
Outdoor At Indicated Indoor Dry Bulb Temp (F) At Indicated Indoor Dry Bulb Temp (F)
Temp (F) 60 70 75 80 60 70 75 80
–8 15.8 15.6 15.4 15.2 3.3 3.7 4.0 4.2
–3 18.3 18.0 17.8 17.6 3.4 3.8 4.0 4.3
2 21.0 20.6 20.3 20.0 3.5 3.9 4.1 4.4
7 23.9 23.3 23.0 22.6 3.6 4.0 4.2 4.4
12 26.8 26.1 25.7 25.4 3.7 4.1 4.3 4.5
17 29.9 29.1 28.7 28.2 3.8 4.1 4.4 4.6
22 33.1 32.2 31.7 31.2 3.8 4.2 4.4 4.7
27 36.5 35.4 34.9 34.4 3.9 4.3 4.5 4.8
32 39.9 38.8 38.2 37.6 4.0 4.4 4.6 4.9
37 43.4 42.0 41.4 40.8 4.1 4.5 4.7 5.0
42 46.8 45.4 44.7 44.1 4.2 4.6 4.8 5.1
47 56.0 54.2 53.4 52.7 4.3 4.7 4.9 5.2
52 60.0 58.1 57.3 56.5 4.4 4.8 5.0 5.3
57 64.1 62.1 61.1 60.3 4.5 4.9 5.2 5.4
62 68.4 66.3 65.4 64.4 4.6 5.1 5.3 5.6
67 72.7 70.6 69.6 68.5 4.8 5.3 5.5 5.8
72 77.3 75.0 73.9 72.7 5.0 5.4 5.7 6.0
Notes:
1. Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand
defrost cycle.