Performance
Data
Table PD-6 — Three Phase Net Heating Capacities (kW) WSC072AD,T at 4,080 m
3
/h (SI)
Integrated Heating Capacity (kW) Total Power (kW)
Outdoor At Indicated Indoor Dry Bulb Temp (C) At Indicated Indoor Dry Bulb Temp (C)
Temp (C) 15 21 24 27 15 21 24 27
–24 6.3 6.2 6.2 6.2 4.5 4.9 5.1 5.3
–21 7.3 7.2 7.1 7.1 4.6 5.0 5.2 5.4
–18 8.3 8.1 8.1 8.0 4.7 5.0 5.2 5.5
–15 9.3 9.1 9.0 8.9 4.7 5.1 5.3 5.6
–12 10.4 10.2 10.1 9.9 4.8 5.2 5.4 5.6
–9 11.5 11.2 11.1 11.0 4.9 5.3 5.5 5.7
–6 12.6 12.3 12.2 12.1 5.0 5.4 5.6 5.8
–3 13.8 13.5 13.3 13.1 5.0 5.5 5.7 5.9
0 15.0 14.7 14.5 14.3 5.1 5.6 5.8 6.0
3 16.3 15.9 15.7 15.5 5.2 5.7 5.9 6.2
6 17.6 17.2 16.9 16.7 5.3 5.8 6.0 6.3
9 21.0 20.5 20.3 20.0 5.4 5.9 6.1 6.4
12 22.6 22.0 21.8 21.5 5.5 6.0 6.2 6.5
15 24.2 23.6 23.3 23.0 5.6 6.1 6.4 6.7
18 25.8 25.2 24.9 24.6 5.8 6.2 6.5 6.8
21 27.5 26.8 26.5 26.1 5.9 6.4 6.7 7.0
24 29.2 28.2 27.9 27.5 6.0 6.5 6.8 7.1
Notes:
1. Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand
defrost cycle.
Table PD-6a — Three Phase Net Heating Capacities (MBH) WSC072AD,T at 2,400 CFM (IP)
Integrated Heating Capacity (MBh) Total Power (kW)
Outdoor At Indicated Indoor Dry Bulb Temp (F) At Indicated Indoor Dry Bulb Temp (F)
Temp (F) 60 70 75 80 60 70 75 80
–8 23.4 23.2 23.0 22.9 4.6 4.9 5.1 5.3
–3 26.6 26.2 26.0 25.8 4.7 5.0 5.2 5.4
2 29.8 29.2 29.0 28.7 4.7 5.1 5.3 5.5
7 33.1 32.5 32.1 31.8 4.8 5.2 5.4 5.6
12 36.5 35.8 35.4 35.0 4.9 5.2 5.4 5.6
17 40.1 39.2 38.8 38.4 4.9 5.3 5.5 5.7
22 43.5 42.6 42.1 41.8 5.0 5.4 5.6 5.8
27 47.2 46.2 45.7 45.2 5.1 5.5 5.7 5.9
32 51.1 50.0 49.5 48.9 5.2 5.6 5.8 6.0
37 55.1 53.9 53.3 52.7 5.3 5.7 5.9 6.1
42 59.1 57.9 57.2 56.6 5.3 5.8 6.0 6.2
47 70.4 68.9 68.1 67.3 5.4 5.9 6.1 6.3
52 75.3 73.6 72.8 71.9 5.5 6.0 6.2 6.5
57 80.3 78.5 77.6 76.7 5.6 6.1 6.3 6.6
62 85.4 83.5 82.6 81.6 5.7 6.2 6.4 6.7
67 90.6 88.6 87.6 86.5 5.9 6.3 6.6 6.9
72 95.9 93.8 92.7 91.5 6.0 6.5 6.7 7.0
Notes:
1. Net heating capacity and power include indoor fan heat at ARI ESP. To obtain net heating at other conditions, subtract fan heat at this condition and add fan heat at new condition.
2. Integrated heating capacities and power include the effects of defrost in the frost region. All heating capacities and power are at 70 % outdoor relative humidity and demand
defrost cycle.