340 9th HIy Reserve Reserve x100
344 13th HIy Reserve Reserve x100
350 3rd HVb 3rd HVb Reserve x100
354 7th HVb 7th HVb Reserve x100
358 11th HVb 11th HVb Reserve x100
364 THD Vb THD Vb Reserve x100
368 5th HIb 5th HIb Reserve x100
DEFINING MULTIPLICATION FACTOR
• Hz has a multiplication factor of 100. If Hz is 48.33, and then it is sent as 4833.
• For providing resolution, all parameters except PF are multiplied with 100
before transmitting. Thus if the KVA value is 278.99, it is sent out as 27899. PF
has MF of 1000, instead of 100. Thus, For LAG side PF value of 0.987 is sent
as 987.For For LEAD side PF value of 0.987 is sent as 1987. Here for LEAD
side PF, 1000 is added with PF value to indicate LEAD side PF.
• DG status has MF of 1. if DG is ON, it will send 1 else it will send 0.