Owner’s Manual
1111 W. 35th Street, Chicago, IL 60609 USA • www.tripplite.com/support
Copyright © 2018 Tripp Lite. All rights reserved. SmartPro
®
is a registered trademark of Tripp Lite.
Español 21
Français 41
SmartPro
®
2U Rackmount
Intelligent, Line-Interactive UPS System
(with Lithium Iron Phosphate Battery)
120V Sine Wave Output • 1500VA - 2200VA Capacity
Models: SMART1500RM2UL, SMART2200RM2UL
(Series Numbers: AG-8897, AG-0163)
Not suitable for mobile applications.
PROTECT YOUR INVESTMENT!
Register your product for quicker service
and ultimate peace of mind.
You could also win an
ISOBAR6ULTRA surge protector—
a $100 value!
www.tripplite.com/warranty
18-01-271-933440.indb 1 1/25/2018 3:23:13 PM

Questions and Answers

  • R
    Robert BarryAug 10, 2025
    What to do if my Tripp Lite SmartPro SMART1500RM2UL UPS shows a Non-Critical Battery Protection Fault?
    • M
      Maureen RothAug 10, 2025
      If your Tripp Lite UPS displays a Non-Critical Battery Protection Fault, it's likely due to the battery experiencing extreme conditions like overcurrent or over-temperature. To resolve this, reduce the load on the UPS, allow it to return to room temperature, recharge the battery for 24 hours, and then restart the UPS if needed.
  • J
    Jonathan ShermanAug 20, 2025
    What to do if my Tripp Lite UPS shows a Charger Fault?
    • B
      bellmelissaAug 20, 2025
      If your Tripp Lite UPS indicates a Charger Fault, it could be because the charge current exceeded its tolerance for more than 10 seconds, or the battery voltage hasn't reached the level needed to start the UPS. Make sure the battery has been charging for 24 hours. Then, restart the UPS or reset the fault by pressing 'Enter/Mute' to return to normal operation.
  • L
    Lisa CaseyAug 31, 2025
    What to do if my Tripp Lite UPS is showing a Critical Battery Protection Fault?
    • E
      elizabeth44Aug 31, 2025
      If your Tripp Lite UPS is showing a Critical Battery Protection Fault, it indicates a component malfunction. Turn off the UPS and contact Tripp Lite for assistance, as this condition requires attention from qualified Tripp Lite technicians.

Tripp Lite SmartPro SMART1500RM2UL Specifications

General IconGeneral
Form FactorRackmount
Input Voltage120V
Output Voltage120V
Number of Outlets8
Interface PortsDB9 Serial, USB
Input Plug TypeNEMA 5-15P
Frequency50 / 60 Hz
Waveform TypeSine Wave
Transfer Time2-4 ms
Typical Recharge Time8 hours
Power Capacity1500 VA
Battery TypeSealed Lead Acid (SLA)
Operating Temperature32 to 104 degrees F (0 to 40 degrees C)
Operating Humidity0% to 95% (non-condensing)