EasyManua.ls Logo

Trox LVC - Page 19

Trox LVC
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Control constant volume flow rate q
vmin
Fig. 14: Constant volume flow rate q
vmin
After applying the 24 V supply voltage, the controller
throttles the volume flow rate to the value set on the
q
vmin
potentiometer
. A setpoint value signal is not
required. The current actual value volume flow rate can
be tapped at the terminal (U).
Variable volume flow control q
vmin
…q
vmax
Fig. 15: Variable volume flow control
If the volume flow rate is to be specified by a higher-
level controller (e.
 g. for room temperature, air quality or
a DDC outstation), its 0–10 V DC output must be con-
nected by at least 2 wires (terminals 1 and 3) to the ter-
minals for the control signal (w) of the Easy controller in
accordance with the connection diagram. With a
common 24 V supply voltage, it should be noted that
terminal 1 on the Easy controller is also the ground for
the control signal.
Switching between volume flow rates q
vmin
and q
vmax
Fig. 16: Switching between volume flow rates q
vmin
and
q
vmax
If the volume flow rate between two constant values can
be switched (e.
 g., day/night switching), it is possible to
switch over between the volume flow rate setpoint
values specified by the q
vmin
and q
vmax
potentiometers
using an on-site volt-free switch contact.
Switch S1 open - q
vmin
Switch S1 closed - q
vmax
Parallel connection
Fig. 17: Parallel connection
If multiple Easy controllers are to be switched simulta-
neously with a switch contact between q
vmin
and q
vmax
,
the S1 switch must be designed as a changeover
switch, and the contact for q
vmin
operation must be con-
nected to the ground (terminal 1)
Wiring
Connection diagrams
Easy control component for VAV terminal units 19

Table of Contents

Related product manuals