6.1.3 Setting examples
Example 1: TVR / 200 / Easy
Nominal volume flow rate q
vnom
of the control unit - 1459 m³/h
Required volume flow rate control range - q
vmin
: 400 m³/h to q
vmax
: 1000 m³/h
Billing solution:
q
vmin
: 400 m³/h / 1459 m³/h × 100 28%
q
vmax
: 1000 m³/h / 1459 m³/h × 100 69%
Example 2: TVJ / 400 x 200 / Easy
Nominal volume flow rate q
vnom
of the control unit - 2592 m³/h
Required volume flow rate control range - q
vmin
:
650 m³/h to q
vmax
: 2250 m³/h
Billing solution:
q
vmin
: 650 m³/h / 2592 m³/h × 100 25%
q
vmax
: 2250 m³/h / 2592 m³/h × 100 87%
Commissioning and operation
Setting of the control component > Setting examples
Easy control component for VAV terminal units 23