EasyManua.ls Logo

Trox LVC - Page 34

Trox LVC
36 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Easy controller SMV-D3A
Supply voltage
24 V AC ± 20%, 50/60 Hz
Supply voltage
24 V DC −10/+20%
Power rating
6 VA max.
Power rating
3 W max.
Run time for 90° 110 – 150 s
Setpoint value signal input 0 – 10 V DC, Ra > 100 kΩ
Actual value signal output 0 – 10 V DC, max. 0.5 mA
IEC protection class III (protective extra-low voltage)
Protection level IP 20
EC conformity EMC to 2014/30/EU
Easy controller TROVE-024T-05I-DD15
Supply voltage
24 V AC ± 20%, 50/60 Hz
Supply voltage
24 V DC −10/+20%
Power rating
4 VA max.
Power rating
Max. 2.5 W
Run time for 90° 100 s
Setpoint value signal input 0 – 10 V DC, Ra > 100 kΩ
Actual value signal output 0 – 10 V DC, max. 0.5 mA
IEC protection class III (protective extra-low voltage)
Protection level IP 42
EC conformity EMC to 2014/30/EU
Technical data
Easy control component for VAV terminal units34

Table of Contents