U s e r I n s t r u c t i o n s
Eco-Net 128 Control Unit
InMn 26 UCESTD
it Rev.1.02
TURBO s.r.l. Dust Filter Components
Via Po 33/35 20811 Cesano Maderno (MB) Italy Tel ++39 0362 574024 Fax ++39 0362 574092
19
Functionality
Cleaning with fan off (Post-Cleaning)
This function allows a cleaning cycle to be run with the fan off. Its activation is automatic in "Auto matic"
and "Proportional" modes, when the pressure differential drops over the value set in the Fan On/Off dP"
parameter of the Advanced Set Up menu. It is possible to repeat the function by configuring the "Fan
Off Cleaning" parameter.
Dedicated parameters are available to carry out the Post-Cleaning function; "Pulse time" and "Cycle
time" in the Advanced Set Up menu.
The function can also be carried out in Manual
and “Special Manual operating modes,
connecting the contact of the fan status to
terminals 4-5 of connector P15.
Precoating
The function allows precoating to be performed. This is a specific treatment of the filtering elements,
which is carried out with a powder suitable for the purpose, known as "precoating powder". During this
phase, the cleaning cycle is suspended until the “dP precoating” threshold has been reached. This can
be set by the user in the Advanced Set Up menu, as also the activation parameter.
Once the precoating dP threshold has been
exceeded, the control unit will begin the cleaning
cycle, automatically disabling the precoating
function.
Setting number of outputs
It is possible to select the number of outputs (solenoid valves) with which the control unit will carry out
the cleaning cycle, respecting the sequential order, from the first to the last solenoid valve, set in the
basic configuration parameter.
Enabling cleaning from remote control
The control unit has an input contact for remote enabling which, when open, cuts off all control unit
functions. A pressure switch can be connected to the remote enabling input of a PLC or an intelligent
control system.