The following table gives the default values (KPa column) programmed in the control unit on leaving
the factory and, by comparison, the same value with respect to the scales available:
Note (
1
): Scale used to calculate the value with respect to the unit of measurement set
The following criterion must be used to calculate the new value of the pressure thresholds:
Unit of
measurement
Selected (Um)
Calculation
New threshold value dP(Um) = [desired value (Um) x K ]
where:
Um = Unit of measurement selected
K = Multiplier co-efficient
Example:
The pressure unit of measurement (Um) is to be modified from “KPa” to “Inch WC” and the “dP START”
threshold is to be set at 3.2 Inch WC.
Operations to perform:
1) Enter the “Main Set Up” menu;
2) Set the unit of measurement dP(1.5) as “Inch WC”;
3) Modify the “dP Start” threshold value (1.6) introducing the result of the following calculation:
“dP Start” threshold value (Inch WC) = 3.2 Inch WC x K = 3.2 Inch WC x 10 = 00032
4) Use the same calculation to modify all the other thresholds with respect to the new unit of
measurement (Um).