PGM Mode (500, 600)
When the device rotary switches are set to 500 or 600, the device IP address can be changed
using following tools:
− Device WEB server
− TURCK IP address tool
While the rotary switches are set to 500, power up the device. It comes up with the last IP ad-
dress that was saved in the EEPROM memory. It can be either the factory default IP address
192.168.1.254 or the last assigned IP address whatever it is.
PGM (500) and Web Server
To login into the Web server as administrator use following procedure:
− Set rotary switches to 500 and power-up device
− If IP address has never been assigned before, enter 192.168.1.254 into Web browser
− If IP address is known, enter the device current IP address into Web browser
− If IP address is unknown, read the “Factory Reset Mode (900)” to reset device to factory
default setup. IP address
− When device web server starts, enter “password” into “Password” field and click “Login”