TBEN-LG EtherNet/IP
TM
Configuration Guide
TURCK 3000 Campus Drive Minneapolis, MN 55441-2656 40
Phone: 763.553.7300 Toll Free: 800.544.7769 Fax: 763.553.0708 www.turck.us
The device configuration data consist of parameters that are read / write enabled. Pa-
rameters are set while the controller is in the program (offline) mode. Configuration is saved in
the controller. The controller always pushes configuration data to the device during PLC down-
load, or at device power-up, when connection between the controller and the device is in pro-
cess of configuring (ForwardOpen).
TBEN-LG Configuration Parameters
Item
Parameter
name
Description
TBEN Digital Inputs
Pulse_stretching
Trigger to an internal TOF
timer, (available for input
channels only)
IStx
It is an input signal OFF timer. The time base is
10ms. For example a value of 14 means 140ms.
Pulse stretch range [0-127].
Default = 0 value [Pulse stretching is disabled].
Input_Inversion Inv.Ix
Inversion of input signal. A 0 means that an acti-
vated input (green LED on) is transmitted as a
logical 1 in the process data.
A 1 means that an activated input (green LED
on) is transmitted as a logical 0 in the process
data.
Default = 0
TBEN Digital Outputs
Disable_Auto_Recovery
Recovery mode of the out-
puts in case of short circuit
SROx
The behaviour of an output that recovers from
short condition is controlled by this parameters:
= 0, automatic recovery is enabled; Output turns
ON after short condition
= 1, automatic recovery is disabled; Output stays
OFF after short condition.
Default = 0
Output_Enable Out Enable x
Only available on DXP devices.
0 = output driver is not be enabled.
1 = output driver is enabled
Default = 1