TBEN EtherNet/IP Configuration
Following section provides information how to configure TBEN device with Rockwell Automation
Logix controllers. There are two configuration methods which depend on a controller revision:
Configuration using EDS file ( Electronic Data Sheet):
It is supported only by Logix controllers firmware revision 20.00.00 and above.
Configuration using Ethernet Generic device profile:
It is supported by all Logix controllers
TBEN Configuration Using EDS Files
The EDS file which supports configuration assembly may be imported into RSLogix5000 project.
The Logix Designer creates device profile based on EDS and saves device configuration in the
project. The controller pushes configuration data to the device whenever connection between
them is established.
The TBEN-LG configuration procedure includes following steps:
Configure EtherNet/IP User Interface
Create RSLogix5000 project
Install Device EDS File(s)
TBEN General Configuration
TBEN Connection Configuration
Module Definition Data Format
Communication RPI, Multicast / Unicast
TBEN Input, Output and Configuration Data Tags