TBEN-LG EtherNet/IP
TM
Configuration Guide
TURCK 3000 Campus Drive Minneapolis, MN 55441-2656 27
Phone: 763.553.7300 Toll Free: 800.544.7769 Fax: 763.553.0708 www.turck.us
Restore Mode (0)
When rotary switches are set to 0 and device power cycled, the device recovers only IP address
to factory default value:
IP address: 192.168.1.254
Mask: 255.255.255.0
Gateway: 192.168.1.1
The device responds to PING command, but it does not operate when switches are set to 0. At
this point it is necessary either, to assign new IP using address tools as described earlier, or
simply dial rotary switches between xx=1,…, 253; to set address as 192.168.1.x.
Factory Reset Mode (900)
The device resets itself to factory default settings, as follows:
Set the rotary switches to 900 position
Power up the device (the BUS LED solid red) and wait 10 sec
Set the rotary switches to 600 (PGM-DHCP mode)
Cycle power to the device