TFP1112_EN  Page 7 of 10
valve’s  low  body  drain  valve,  to  bleed  o 
any excess water  above the  priming  level. 
Reclose  the  low  body  drain  valve,  return 
system  pressure  to  its  normal  value,  and 
then re‑open the Accelerator Control Valve.
Step  14. 
Partially  open  the  main  control 
valve.  Close  the  main  drain  valve  as  soon 
as water discharges from the drain connec‑
tion,  and  then  completely  open  the  main 
control valve. The re protection system is 
now ready for service.
NOTE
After  placing  a  re  protection  system  in  ser‑
vice, notify the proper authorities and advise 
those responsible for monitoring proprietary 
and/or central station alarms.
Care and 
Maintenance
The  following  procedures and  inspections 
should  be  performed  as  indicated,  in  ad‑
dition  to  any  specic  requirements  of  the 
NFPA, and any impairment must be imme‑
diately corrected. 
The  owner  is  responsible  for  the  inspec‑
tion, testing, and maintenance of their re 
protection  system  and  devices  in  compli‑
ance  with  this  document,  as  well  as  with 
the  applicable  standards  of  the  National 
Fire  Protection Association  (e.g., NFPA 25), 
in addition to the standards of any author‑
ity  having  jurisdiction.  The  installing  con‑
tractor or product manufacturer should be 
contacted relative to any questions. 
It is recommended that automatic sprinkler 
systems  be  inspected,  tested,  and  main‑
tained by a qualied Inspection Service. 
The Model ACC‑1 Accelerator must be main‑
tained and serviced in accordance with the 
following instructions: 
NOTE 
If an Accelerator is to be temporarily taken out 
of service, then the proper authorities and all  
personnel who may be aected must be noti‑
ed. 
Before  performing  an  alarm  test,  notify  the 
proper authorities and all personnel who may 
be aected. 
Before closing  a  re  protection system  main 
control  valve for  inspection  or  maintenance 
work on the re protection system that it con‑
trols, permission to shut down the aected re 
protection system must be obtained from the 
proper authorities and all personnel who may 
be aected by this action must be notied. 
Accelerator Inspection Procedure 
It is recommended that the following Accel‑
erator inspection procedure be performed 
at  least  annually,  preferably  in  the  fall  or 
winter  of  the  year.  This  procedure  must 
also be used whenever ooding the system 
would expose the water to freezing condi‑
tions.
Step  1.  Verify  that  the  Reset  Knob  is 
screwed in. 
Step  2.  Close  the  system’s  main  control 
valve and open the main drain valve to re‑
lieve  the  supply  pressure  to  the  dry  pipe 
valve. 
Step 3. 
Verify  that the Accelerator Control 
Valve is open. 
Step 4. 
Open the Inspector’s Test Connec‑
tion. Verify that the time to Accelerator trip 
is essentially the same as in previous tests. A 
momentary burst of air from the Automatic 
Drain  Valve  indicates  that  the  Accelerator 
has tripped. 
NOTE 
As the system pressure is decreasing, check for 
any sign of water being discharged from the 
Accelerator Relief Port. 
Step  5.  Depress  the  plunger  of  the  Auto‑
matic  Drain  Valve.  A  steady  stream  of  ex‑
hausting  air  indicates  that  the  Accelerator 
has  properly  latched  in  the  Tripped  posi‑
tion. 
Step 6. Close the Accelerator Control Valve 
and the Inspector’s Test Connection. 
Step 7. Clean out the Strainer at the Accel‑
erator inlet. 
NOTE 
A clogged strainer can prevent the Accelera‑
tor from properly tripping the dry pipe valve. 
Step 8. Reset the Accelerator in accordance 
with Steps 7 through 14 of the Setting Pro‑
cedure Section.  
System Inspection Procedure
It  is  recommended  that  the  following  Ac‑
celerator  and  dry  pipe  valve  inspection 
procedure  be  performed  at  least  annu‑
ally, preferably in the spring or summer of 
the year. This procedure can only be used 
whenever there is no danger that ooding 
the system will expose the water to freezing 
conditions. 
Step  1.  Verify  that  the  Reset  Knob  is 
screwed in. 
Step 2. Open the Inspector’s Test Connec‑
tion. Verify that tripping of the Accelerator 
operates the dry pipe valve and that water 
is delivered out of the Inspector’s Test con‑
nection  within  the  elapsed  time  required 
by the authority having jurisdiction. 
NOTE 
As the system pressure is decreasing, check for 
any sign of water being discharged from the 
Accelerator Relief Port. 
Step 3. 
Reset the accelerator and dry pipe 
valve in accordance with the Setting Proce‑
dure Section. 
Trouble Shooting 
Refer to the following subsections, as appli‑
cable. If the designated instructions do not 
remedy the particular problem, refer to the 
Accelerator  Disassembly  and  Reassembly 
subsection. 
Water Discharge From Accelerator Relief 
Port
Use  the  following  instructions  if  water  is 
discharged from the Accelerator Relief Port 
during a trip. 
Step 1. Verify that the connection from the 
Accelerator to the system piping is installed 
in accordance with Step 4 of the Installation 
Section. Correct if necessary. 
Step 2. Investigate for and correct any con‑
dition  which  could  result  in  an  excessive 
build‑up  of  drain  back  and/or  condensate 
water. 
Step  3. 
Review  procedures  which  were 
used to set the  Accelerator. Failure to per‑
form  Step  5  of  the  Setting  Procedure  can 
permit a small amount of water to enter the 
Pilot Chamber of the Accelerator.  
Slow Fill of Dierential Chamber 
Use the following instructions if the time to 
ll the Dierential Chamber is longer than 
the maximum value indicated in Step 11 of 
the Setting Procedure Section. 
Step  1.  Check  to  see  that  the  Accelerator 
was reset  per Step 8  of  the Setting Proce‑
dure Section. 
Step  2.  Close  the  system’s  main  control 
valve and open the main drain valve. 
Step 3. 
Check for any sign of external leak‑
age  past  the  Accelerator  Pressure  Gauge, 
Vent,  and  Restriction  Access Plug  connec‑
tions.
Step 4. 
Check for any sign of external leak‑
age past the Reset Knob and Cover Gasket. 
Step 5. Close the Accelerator Control Valve. 
Step 6. Gently insert an M2 (3/32”) or small‑
er  diameter  probe  into  the  Relief  Port.  If 
the probe can be inserted more than 6 mm 
(1/4”) then the Lever has not reset and the 
Accelerator must be disassembled for inter‑
nal inspection. See the instructions for Ac‑
celerator Disassembly and Reassembly.