TFP1090 
Page 10 of 26
Installation
NOTICE
Alteration of the trim may prevent the 
Model DPV-1  Valve from functioning 
properly, as well as void approvals and 
the manufacturer’s warranties.
Failure to latch open the Clapper 
Assembly prior to a system hydro-
static test may result in damage to the 
Clapper Assembly.
The Model DPV-1 Valve must be 
installed in a readily visible and acces-
sible location.
The DPV-1 Valve and associated trim 
must be maintained at a minimum tem-
perature of 4°C.
Heat tracing of the Model DPV-1 Valve 
or its associated trim is not permit-
ted. Heat tracing can result in the for-
mation of hardened mineral deposits 
that are capable of preventing proper 
operation.
Install TYCO Model DPV-1 Dry Pipe 
Valves in accordance with the follow-
ing criteria:
• 
The  Model DPV-1 Dry Pipe Valve 
must be installed with factory 
assembled trim.
• 
Suitable provision must be made 
for disposal of drain water. Drainage 
water must be directed such that it 
will not cause accidental damage to 
property or danger to persons.
• 
Installation of an Air Maintenance 
Device, as described in the Technical 
Data Section, is  recommended.
• 
It is best practice to install an 
appropriately rated and listed relief 
valve upstream of the Model DPV-1 
Dry Pipe Valve, between the inlet 
of the DPV-1 Valve and any check 
valves or back ow preventers, to 
ensure transient increases in water 
pressure do not cause unintended 
operation of the DPV-1 Valve.
• 
An Inspector’s Test Connection must 
be provided on the system piping at 
the most remote location from the 
Model DPV-1 Dry Pipe Valve.
• 
Conduit and electrical connections 
are to be made in accordance with 
the requirements of the authority 
having jurisdiction.
• 
Before a system hydrostatic test 
is performed in accordance with 
the standards recognized by the 
Approval agency, in addition to any 
other authorities having jurisdic-
tion, the Clapper Assembly is to be 
manually latched open (see Figure 
3D); the Automatic Drain Valve (see 
Water Supply 
Pressure, bar
System Air 
Pressure 
Range, bar
1,4 0,7
4,1 1,0 - 1,6
5,5 1,4 - 1,9
6,9 1,7 - 2,3
8,3 2,1 - 2,6
10,0 2,4 - 3,0
11,4 2,8 - 3,3
12,8 3,1 - 3,7
14,1 3,4 - 4,0
15,5 3,8 - 4,3
16,0 4,1 - 4,6
Pressure 
(bar)
Minimum 
(sec.)
Maximum 
(sec.)
1,4 24 160
1,7 18 116
2,1 15 92
2,8 10 60
3,5 8 48
4,1 6 36
TABLE C 
ACCELERATOR 
DIFFERENTIAL CHAMBER 
FILL TIMES TO 0,7 BAR
TABLE B 
SYSTEM AIR PRESSURE 
REQUIREMENTS
Figures 7 to 18) is to be temporarily 
plugged; and, the Handhole Cover 
Bolts are to be tightened using a 
cross-draw sequence.
Valve Setting 
Procedure
Perform this procedure when initially 
setting the Model DPV-1 Dry Pipe 
Valve; after an operational test of the 
fire protection system; or, after system 
operation due to a fire.
See Figures 7 to 18 as applicable 
for the given riser arrangement and 
proceed as follows:
Step 1.  Close the Main Control Valve, 
and close the Air Supply Control Valve. 
If the Model DPV-1 Dry Pipe Valve is 
equipped with a Dry Pipe Valve Accel-
erator, close the Accelerator Control 
Valve.
Step 2.  Open the Main Drain Valve 
and all auxiliary drains in the system. 
Close the auxiliary drain valves after 
water ceases to discharge. Leave the 
Main Drain Valve open.
Step 3.  As applicable, place the 
Three-Way Alarm Control Valve in the 
open position.
Step 4.  Verify that the Automatic Drain 
Valve has stopped draining to deter-
mine the Model DPV-1 Valve is com-
pletely drained.
Step 5.  As necessary, replace all 
sprinklers that have operated. Replace-
ment sprinklers must be of the same 
type and temperature rating as those 
which have operated.
NOTICE
In order to prevent the possibility of 
a subsequent operation of an over-
heated solder type sprinkler, any solder 
type sprinklers which were possibly 
exposed to a temperature greater than 
their maximum rated ambient must be 
replaced.
Step 6.  Push down on the Reset Knob 
as shown in Figure 3E to allow the 
Clapper Assembly to reseat.
Step 7.  Pressurize the system with 
air (or nitrogen) to 0,7 bar, and then 
individually open all auxiliary drain 
valves in the system piping to drain 
any remaining water in trapped sec-
tions. Close each drain valve as soon 
as water ceases to discharge. Also par-
tially open the Low Body Drain Valve in 
the valve trim to assure that the riser 
is completely drained. Close the Low 
Body Drain Valve as soon as water 
ceases to discharge.
Step 8.  See Table B and then restore 
the system to the normal system air 
pressure as necessary to hold the 
Model DPV-1 Valve closed.
Step 9.  Verify that there is not any air 
discharging from the Automatic Drain 
Valve.
The absence of air discharging from 
the Automatic Drain Valve is an indica-
tion of a properly set air seat within the 
Model DPV-1 Valve. If air is discharging, 
see the Care and Maintenance section 
under Automatic Drain Valve Inspection 
to determine/correct the cause of the 
leakage problem.
Step 10. If the Model DPV-1 is 
equipped with a Dry Pipe Valve Accel-
erator, reset the Dry Pipe Valve Accel-
erator in accordance with Steps 10A 
through 10H. Otherwise, proceed to 
Step 11.