TFP1090 
Page 11 of 26
Step 10A. While holding the plunger 
of the Automatic Drain Valve 
depressed, open the Accelerator 
Control Valve one-quarter turn and 
allow the water in the Accelerator 
piping to blow out. After water spray 
stops discharging, close the Accel-
erator Control Valve and then release 
the plunger.
Step 10B. Slowly remove the Vent 
Plug located in the front of the Accel-
erator Cover and bleed off any resid-
ual air pressure in the Differential 
Chamber.
Step 10C. Unscrew (counter-clock-
wise rotation) the knurled Reset 
Knob at the front of the Accelera-
tor until it resists further turning. A 
click, which is the sound of the Lever 
snapping back into the Set Position, 
may be heard. Screw the Reset Knob 
back in until it is finger tight.
NOTICE
Do not wrench on the Reset Knob, 
since damage may result. The Reset 
Knob will turn with finger torque only.
Step 10D. Replace the Vent Plug.
Step 10E. Verify that the system air 
pressure has returned to normal.
Step 10F. Using a watch, note the 
time for the pressure in the Differen-
tial Chamber of the Accelerator to 
increase to 0,7 bar after the Accel-
erator Control Valve is opened. The 
time should be within the range of 
values indicated in Table C for opti-
mum performance of the Accelerator.
If the time to pressurize the Differen-
tial Chamber to 0,7 bar is not within 
the range of values given in the Table 
C, then the Accelerator Control Valve 
should be closed and the corrective 
procedure described in the Care and 
Maintenance Section of ACC-1 Tech-
nical Data Sheet TFP1112 should be 
followed.
Step 10G. When the air pressure 
in the Differential Chamber of the 
Accelerator is equal to that in the 
system, then the Accelerator is set 
and ready for service.
Step 10H. Close the Accelerator 
Control Valve and then slowly open 
the Low Body Drain Valve in the 
trim, to bleed off any excess water 
trapped above the Dry Pipe Valve 
Clapper. Close the Low Body Drain 
Valve, return system pressure to its 
normal value, and then re-open the 
Accelerator Control Valve.
Step 11. Partially open the Main Con-
trol Valve. Slowly close the Main Drain 
Valve as soon as water discharges from 
the drain connection.
Verify that there is not any water dis-
charging from the Automatic Drain 
Valve.
The absence of water discharging from 
the Automatic Drain Valve is an indica-
tion of a properly set water seat within 
the Model  DPV-1 Dry Pipe Valve. If 
water is discharging, see the Care and 
Maintenance section under the Auto-
matic Drain Valve Inspection to deter-
mine/correct the cause of the leakage 
problem.
If there are no leaks, the Model DPV-1 
Dry Pipe Valve is ready to be placed 
in service and the Main Control Valve 
must then be fully opened.
After setting a fire protection system, 
notify the proper authorities and advise 
those responsible for monitoring pro-
prietary and/or central station alarms.
Step 12. Once a week after a valve is 
reset following an operational test or 
system operation, the Low Body Drain 
Valve (and any low point drain valves) 
should be partially opened (and then 
subsequently closed) to relieve drain-
back water. Continue this procedure 
until drain-back water is no longer 
present.
Care and 
Maintenance
The following procedures and inspec-
tions should be performed as indicated, 
in addition to any specific require-
ments of any authority having jurisdic-
tion. Impairments must be immediately 
corrected.
The owner is responsible for the 
inspection, testing, and maintenance of 
their fire protection system and devices 
in compliance with this document, as 
well as with the applicable standards 
of any authority having jurisdiction. The 
installing contractor or product manu-
facturer should be contacted relative to 
any questions.
Automatic sprinkler systems are rec-
ommended to be inspected, tested, 
and maintained by a qualified Inspec-
tion Service.
NOTICE
The operational test procedure and 
waterflow pressure alarm test pro-
cedure will result in operation of the 
associated alarms. Consequently, 
notification must first be given to the 
owner and the fire department, central 
station, or other signal station to which 
the alarms are connected.
Before closing a fire protection system 
Main Control Valve for maintenance 
work on the fire protection system 
that it controls, obtain permission to 
shut down the affected fire protection 
systems must first be obtained from the 
proper authorities and notify all person-
nel who may be affected by this deci-
sion must be notified.
Annual Operation 
Test Procedure
Proper operation of the Model DPV-1 
Dry Pipe Valve (that is, opening of the 
Model DPV-1 Dry Pipe Valve during 
a fire condition) should be verified at 
least once a year as follows:
Step 1.  If water must be prevented 
from flowing beyond the riser, perform 
the following steps:
•  Close the Main Control Valve.
•  Open the Main Drain Valve.
•  Open the Main Control Valve one turn 
beyond the position at which water 
just begins to flow from the Main 
Drain Valve.
•  Close the Main Drain Valve.
Step 2.  Open the system’s Inspector’s 
Test Connection.
Step 3.  Verify that the Model DPV-1 
Dry Pipe Valve has operated, as indi-
cated by the flow of water into the 
system and that all waterflow alarms 
operate properly.
Step 4.  Close the system’s Main Con-
trol Valve.
Step 5.  Reset the Model DPV-1 Dry 
Pipe Valve in accordance with the Valve 
Setting Procedure.
The inside of the valve is recommended 
to be inspected at this time and prior 
to resetting the Model DPV-1 Dry Pipe 
Valve. See Steps 2 to 5 in the Inspec-
tion Procedure section on the Auto-
matic Drain Valve for instructions on 
the inspection of the Clapper Facing.
Periodic Waterflow Alarm 
Test Procedure
Testing of the system waterflow 
alarms should be performed periodi-
cally based on the requirements of the 
authority having jurisdiction. To test the 
waterflow alarm, place the Three-way 
Alarm Test Valve in the “Test” posi-
tion or open the Standard Alarm Test 
Valve, as applicable, which will allow 
a flow of water to the Waterflow Pres-
sure Alarm Switch and/or Water Motor 
Alarm. Upon satisfactory completion 
of the test, place the Three-way Alarm 
Test Valve in the “Open” position or 
close the Standard Alarm Test Valve, 
as applicable.
Water Pressure 
Inspection Procedure
The Water Pressure Gauge is to be 
inspected periodically based on the 
requirements of the authority having 
jurisdiction to ensure that normal 
system water pressure is being 
maintained.