TFP1090 
Page 12 of 26
Air Pressure 
Inspection Procedure
The Air Pressure Gauge is to be 
inspected periodically based on 
the requirements of the author-
ity having jurisdiction to ensure that 
normal system air pressure is being 
maintained.
Automatic Drain Valve 
Inspection Procedure
The Automatic Drain Valve should be 
inspected periodically based on the 
requirements of the authority having 
jurisdiction by depressing the plunger 
and checking to ensure that the Auto-
matic Drain Valve is not discharging 
water and/or air. A discharge of water 
and/or air is an indication that the air 
and/or water seats are leaking, which 
could subsequently cause a false oper-
ation should the intermediate chamber 
become inadvertently pressurized.
If leakage is present, take the Model 
DPV-1 Valve out of service (that is, 
close the Main Control Valve, open 
the Main Drain Valve, close the Air 
Supply Control Valve, remove the Dry 
Pipe Valve Accelerator from service, as 
applicable, by closing the Accelerator 
Control Valve, and open the Inspector’s 
Test Connection to relieve the system 
air pressure to 0 psig as indicated on 
the System Air Pressure Gauge), and 
then after removing the Handhole 
Cover, perform the following steps:
Step 1.  Make sure that the Seat Ring 
is clean and free of any nicks or signifi-
cant scratches.
Step 2.  Remove the Clapper Assem-
bly from the valve by first pulling out 
the Hinge Pin.
Step 3.  Disassemble the Clapper Fac-
ing Retainer from the Clapper so that 
the Clapper Facing can be removed 
and inspected. Make sure that the 
Clapper Facing does not show signs 
of compression set, damage, etc. 
Replace the Clapper Facing if there is 
any signs of wear.
Step 4.  Clean the Clapper Facing, 
Clapper, and Clapper Facing Retainer, 
and then reassemble the Clapper 
Assembly.
Step 5.  Reinstall the Clapper Assem-
bly with its Hinge Pin.
Step 6. Install Handhole Cover:
a.  Align Handhole Cover Gasket and 
Handhole Cover in proper orien-
tation with valve body (Ref. Figure 
1) and hold in place
b.  Apply LOCTITE No. 242 (or equiv-
alent) to Hex Bolt threads
c.  Insert Hex Bolts through Hand-
hole Cover Gasket and Handhole 
Cover, hand-tighten into valve 
body
d.  Using crossdraw sequence to 
assure uniformity, wrench-tighten 
Hex Bolts to appropriate torque 
values (Ref. Table D)
e.  Inspect to assure all Hex Bolts 
are securely tightened
Accelerator 
Inspection Procedure
It is recommended that the Accelera-
tor be inspected periodically based 
on the requirements of the authority 
having jurisdiction to determine proper 
operation of the Accelerator without 
having to trip the Dry Pipe Valve. This 
procedure must also be used whenever 
flooding the system would expose the 
water to freezing conditions.
See Technical Data Sheet TFP1112 for 
guidance with regard to trouble shoot-
ing of the Model ACC-1 Dry Pipe Valve 
Accelerator.
Step 1.  Verify that the Reset Knob is 
screwed in.
Step 2.  Close the system’s Main Con-
trol Valve and open the Main Drain 
Valve to relieve the supply pressure to 
the Dry Pipe Valve.
Step 3.  Verify that the Accelerator 
Control Valve is open.
Step 4.  Open the Inspector’s Test 
Connection. Verify that the time to 
Accelerator trip is essentially the same 
as in previous tests. A momentary 
burst of air from the Automatic Drain 
Valve indicates that the Accelerator has 
tripped.
As the system pressure is decreasing, 
check for any sign of water being dis-
charged from the Accelerator Relief 
Port.
Step 5.  Depress the plunger of the 
Automatic Drain Valve. A steady stream 
of exhausting air indicates that the 
Accelerator has properly latched in the 
Tripped position.
Step 6.  Close the Accelerator Con-
trol Valve and the Inspector’s Test 
Connection.
Step 7.  After the system automatically 
restores itself to its normal air pressure, 
reset the Accelerator and Dry Pipe 
Valve in accordance with the Valve Set-
ting Procedure Steps 10 and 11.
Nominal 
Valve Sizes 
DN
Torque 
Nm
DN65 41
DN80 41
DN100 41
DN150 75
TABLE D 
HANDHOLE COVER BOLTS 
MAXIMUM TORQUE