maintained below -20°F/-29°C. See
Technical Data Sheet TFP1241.
It is recommended that internally gal-
vanized pipe and cast iron fittings be
used for dry pilot lines.
Supervision of the pressure in the dry
pilot actuation system and/or alarm
that separately indicates operation of
the detection system is recommended
and may be required by the authority
having jurisdiction. A dual setting low
pressure alarm switch, such as the
Potter Electric PS40-2A, is suitable for
the service. The recommended pres-
sure settings are as follows:
Low pressure alarm setting at ap-
proximately 6 psi (0,4 bar) below the
minimum pilot line service pressure
requirement shown in Graph C.
Fire alarm setting at approximately
15 psi (1,0 bar) below the minimum
pilot line service pressure require-
ment shown in Graph C.
The Pressure Relief Valve (Ref. Item
D6 - Fig. 6) is factory set to relieve at
a pressure of approximately 45 psi (3,1
bar); however, it may be field adjusted
to a lower pressure, if required.
Page 9 of 20
TFP1350
GRAPH C
2-1/2 INCH (DN65) MODEL DV-3 DELUGE VALVE
DRY PILOT LINE PRESSURE REQUIREMENTS
WATER S
U
PPLY PRESS
U
RE IN PSI
AIR PRESSURE IN PSI
20 17540 60 80 100 120 140 160
30
20
10
0
40
MINIMUM SYSTEM AIR PRESSURE
RANGE OF ACTUATOR OPENING PRESSURE
OBSOLETE