Electric
Actuation
The Electric Actuation Trim forms a
part of the laboratory approval of the
DV-5 Valves and is necessary for their
proper operation.
The Electric Actuation Trim is required
for electric operation of the DV-5 Valve
by a detection system consisting of
electrical devices such as heat sen-
sitive thermostats, smoke detectors,
and/or electric manual pull stations.
Installation dimensions are provided in
Figure 19 (Page 26).
The Solenoid Valve provided in the
valve trim (P/N 52-287-1-124 described
in TFP2180) is rated as follows:
Pressure: 17,2 bar
Voltage: 24 VDC
Power Consumption: 22 Watts
Current Draw: 0,83 Amps
NOTES
Approval by VdS and LPCB is
contin¬gent on the use of the Solenoid
Valve provided with the valve trim. VdS
and LPCB only approve solenoid valves
for use in non-hazardous locations.
Consult with the applicable standards
of the Approval agency regarding in-
stallation criteria pertaining to electric
actuation circuitry.
The Electric Actuation Trim is provided
with a Model ASV-1 Automatic Shut-
Off Valve; consequently, the release
circuit of the releasing panel need only
provide the standard ten minutes of
alarm condition intended to energize
the Solenoid Valve to open. After the
ten minute duration, at which point
should the Solenoid Valve become de-
energized and close (especially while
operating under battery back-up), the
Automatic Shut-Off Valve will have
already automatically closed, there-
by preventing the DV-5 Diaphragm
Chamber from becoming re-pressur-
ized, and preventing an inadvertent
closing of the DV-5 during a fire event.
Diaphragm Supply Strainer
Diaphragm Supply Connection
Water Motor Alarm Connection
Solenoid Valve
DV-5 Valve
Waterflow Switch
Stop Valve
Automatic Drain Valve
Alarm Test Valve
System Drain Valve
(Not used)
Diaphragm Gauge
System Gauge
Water Supply Gauge
Diaphragm Supply Valve
Automatic Shut-Off Valve
Manual Control Station
Alarm Control Valve
Description
B
G
2
C
F
H
J
E
N
1
P
Q
A
R
M
K
L
Q
2
1
R
H
L
P
N
M
K
J
D
F
G
E
A
C
B
Item
FIGURE 6
ELECTRIC ACTUATION
(Refer to Figure 15 thru 18 for specic Bills of Materials)