TFP1450
Page 4 of 28
In the case of Electric/Pneumatic Acti-
vation, a solenoid valve and a dry pilot 
actuator connected in series is used to 
hold the DV-5a Valve closed by locking 
pressure in the diaphragm chamber 
of the DV-5a Valve. In the event of a 
fire, a releasing panel is initiated by a 
fire detection or electric manual pull 
station, to allow the solenoid valve to 
open, and subsequently loss of system 
air pressure due to opening of an auto-
matic sprinkler will result in opening of 
the dry pilot actuator. Opening of both 
the solenoid valve and dry pilot actu-
ator results in operation of the DV-5a 
Valve.
The selection of Electric/Electric versus 
Electric/Pneumatic is related to desired 
system air pressure and system 
volume that affects water delivery time 
restraints.
NOTICE
The DV-5a Valves described herein 
must be installed and maintained in 
compliance with this document, as 
well as with the applicable standards 
of the NATIONAL FIRE PROTECTION 
ASSOCIATION (NFPA), in addition to 
the standards of any other authorities 
having jurisdiction. Failure to do so 
may impair the performance of these 
devices.
The owner is responsible for main-
taining their fire protection system 
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any 
questions.
Technical 
Data
Approvals
UL/C-UL Listed  
FM Approved
Listings and Approvals are based on 
DV-5a being trimmed as described in 
this technical data sheet.
DV-5A Valve
Components for the 1-1/2 thru 8 Inch 
(DN40 thru DN200) DV-5a Valves are 
shown in Figure 1. The DV-5a Valves 
are for vertical installations. They are 
rated for use at a service pressures of 
20 to 300 psi (1,4 to 20,7 bar).
The take-out dimensions are shown 
in Figure 3, and flanged connections 
are available drilled per ANSI, ISO, 
AS, and JIS specifications (Ref. Table 
A). Threaded inlet and outlet connec-
tions are available in NPT or ISO 7/1. 
Threaded port connections are NPT 
threaded.
NOTE: PN16 flanges are pressure rated 
to 16 bar.
Valve Trim
The maximum pressure rating is as 
follows:
• 
Electric/Electric Double Interlock 
Preaction Trim is dependent on 
separately ordered solenoid valve 
per Technical Data Sheet TFP2180.
• 
Electric/Electric Double Interlock 
Preaction Trim when using the 
separately ordered QRS Elec-
tronic Accelerator is based on the 
separately ordered QRS electronic 
Accelerator per Technical Data 
She e t TFP110 0
• 
Electric Pneumatic Double Interlock 
Preaction Trim is the lesser of 
250 psi (17,2 bar) or the sepa-
rately ordered solenoid valve per 
Technical Data Sheet TFP2180
When the system pressure is greater 
than 175 psi (12,1 bar), provision is to be 
made to replace the standard order 300 
psi (20,7 bar) Water Pressure Gauges 
with separately ordered 600 psi (41,4 
bar) Water Pressure Gauges.
If the addition of an Alarm Control Valve 
is desired or required by the local AHJ, 
the Alarm Control Valve noted as Item 
H in Figures 12 and 13 is to be a sepa-
rately ordered electronically supervised 
normally open valve.
External trim connections are NPT 
threaded. EMEA trim is provided with 
NPT x ISO 7/1 thread adapters.
Pressure Loss
Refer to Graph A
Actuation Options
Refer to subsections for Electric/Elec-
tric Actuation or Electric/Pneumatic 
Actuation.
Materials of 
Construction
Valve Body
Epoxy coated ductile iron per ASTM 
A536-77, Grade 65-45-12
Diaphragm Cover
Epoxy coated ductile iron per ASTM 
A536-77, Grade 65-45-12
Diaphragm
Polyester fabric reinforced, TEFLON 
coated, EPDM rubber per ASTM D2000
Diaphragm Cover Fasteners
Aluminum zinc coated steel
Common Hardware Trim
• 
Common hardware pipe ttings are 
galvanized or black as required and 
are malleable per ASME B16.3.
• 
Common hardware pipe nipples are 
galvanized or black as required and 
are Schedule 40 per ASTM A53 or 
A135.
8 Inch (DN200)
6 Inch (DN150)
4 Inch (DN100)
3 Inch (DN80)
2 Inch (DN50)
1-1/2 Inch (DN40)
22-3/8"
(569 mm)
16-3/4"
(425 mm)
13-3/4"
(349 mm)
10-3/16"
(260 mm)
10-3/16"
(260 mm)
27-7/16"
(697 mm)
ARE APPLICABLE TO
ALL END CONNECTION
CONFIGURATIONS
AVAILABLE PER
VALVE SIZE
FIGURE 3 
DV-5a DELUGE VALVE 
TAKE-OUT DIMENSIONS