Document No: LT0255 F3200/NDU AS4428.1 Installation Manual
Installation & Wiring
Issue 1.04 30 June 2004 Page 5-13
W A R N I N G
Apart from the mains supply to the FIP only ELV wiring may enter the cabinet.
Relays must not be used to directly switch medium or high voltage.
+VNBF o─────┐
┌─ SUPERVISION RETURN
| SUP o─────┼─────────┬───────────────────────────────────────┐
|
ANCIL| NC o─────┘ <- ALTERNATIVE
1 |
| COM o───────┬───────┴───┬───────────┬───────────┬───────────┤
└─
╒╧╕ ┌┴┐ ┌┴┐ ┌┴┐ ┌┴┐
1N4004 └┬┘ └┬┘ └┬┘ └┬┘
└┬┘
0V o───────┴───────────┴───────────┴───────────┴───────────┘
SUPPRESSION DOOR HOLDERS
DIODE
A. WITH SUPERVISION OF LOOP POSITIVE WIRING ONLY
+VNBF o─────┐
┌─ SUPERVISION RETURN
| SUP o─────┼───────────────────────────────────────────┐
|
ANCIL| NC o─────┘
1 |
| COM o───────┬───────┬───────┬───────┬─────┬─────┬───┐
└─
╒╧╕ ┌┴┐ ┌┴┐ ┌┴┐ ╒╧╕ ┌─┴─┐ o NO
* └┬┘ └┬┘ └┬┘ * /
└┬┘ └┬┘ └─┬─┘ o COM
0V o───────┴───────┴───────┴───────┴─────┴─────┘ └─┘
* SUPPRESSION DOOR HOLDERS +24V RELAY
DIODE
B. WITH SUPERVISION OF LOOP POSITIVE AND NEGATIVE WIRING
FIG 5.4.1
EXAMPLE OF DOOR HOLDER WIRING WITH SUPERVISION