F3200/NDU AS4428.1 Installation Manual Document No: LT0255
Installation & Wiring
Page 5-14 30 June 2004 Issue 1.04
+VBF1 o─────┐
┌─
| SUP o──┐
|
ANCIL| NC o──┘
1A |
| NO o─────┘ LOAD
| (SEE NOTE)
| COM o───────────────────────────────────────────┬───────────┐
└─
┌┴┐ ╒╧╕
└┬┘
└┬┘
0V o───────────────────────────────────────────┴───────────┘
SUPPRESSION
DIODE
Note: For a load of less than 400 Ohms a diode of suitable current rating must be added in
series with the load at the load as shown below.
──────┬───┐ ──────┐
┌─┴─┐╒╧╕ ┌┴┐
LOAD ││ DIODE DIODE
└─┬─┘└┬┘ ╘╤╛
├───┘ OR
├───┐
┌┴┐ ┌─┴─┐╒╧╕
DIODE LOAD ││ DIODE
╘╤╛ └─┬─┘└┬┘
0V ──────┘ 0V ─────┴───┘
FIG 5.4.2
EXAMPLE OF PLANT RELAY WIRING WITH SUPERVISION
FIGURE 5.4.3
EXAMPLE OF SUPERVISING MULTIPLE BRANCHES OF MULTIPLE LOADS
VBF
NO
C
NC
SUP
0V
EOLR
Evac
+V
Ext Def-
0V
Ancil
Relay
Evac-
EOLR
Bell Monitor Rev 3
Up to 3 branches of
Load.
Evac+