T1200
MARINEC-P-A
3 02/14
PAGE 62 of 67
22. Appendix
22.1 EN54 Optional Functions with
Requirements
The T1200-C
panel has the following EN54 optional
functions:
Clause 7.8 Outputs to fire alarm devices.
Clause 7.9 Outputs to fire alarm routing
equipment.
Clause 7.10 Outputs to Fire Protection
Equipment.
Clause 8.4 Total loss of the power supply.
Clause 8.9 Output to fault warning routing
equipment.
Clause 10 Test condition.
22.2 Ancillary Functions Not Required
By EN54
The T1200
panel offers several auxiliary functions
that are not required/allowed by EN54. These are:
Fire [Routing], Fire Protection and Fault
[Routing] outputs can be configured to be volt-
free change over contacts.
Detection zones can be configured as non-
latching.
Detection zones can be configured for
Intrinsically Safe applications.
Class change input - operates sounders briefly
to signal class changes in educational
institutions. [Land-based feature].
Reset relay to interrupt power supplies to
external equipment that needs to be reset in
tandem with the T1200-C panel (e.g. IR Beam
Detectors).
Engineer configurable features:
o To require the silencing of the fire alarm
condition prior to enabling the fire alarm
condition reset.
o To inhibit the operation of the Fire
Protection Output for a fire condition on a
zone configured as non-latching.
o To inhibit the silencing of fire alarm
devices and resetting of the fire alarm
condition for a period of 3 minutes after a
fire alarm condition occurs.
o To prevent fire alarm devices operating
for any fire alarm condition other than the
Manual Fire Alarm/Muster condition.
o To disable the panel buzzer.
Open collector outputs for Manual Fire
Alarm/Muster active, buzzer active,
disablement active, zonal fire O/Ps for each
zone up to zone 4.
Remote inputs for remote Manual Fire
Alarm/Muster, remote reset and remote silence
alarms.
One Man Sounder Test [see 16.6].
Latching fault mode where all fault conditions
latch until the panel is manually reset.
Restore default configuration of zones and
outputs.
Selectable options for operation in the Manual
Fire Alarm or Muster modes.
Muster alarm capable of being initiated, locally
or from a repeater panel, even if panel
processors fail.
Dimmable LEDs on the display.