64
Parameter Description 5 PANS 115V 5 PANS 230V
SELF CONTAINED 230V
TROLLEY
ADR serial address [num] 1
1 1 1
EVO alarm intervention super-parameter [num] 0
0 0 0
IS1 probes and door input configuration super-parameter [num] 155
155 155 155
IS2 digital input configuration super-parameter [num] 8
8 8 8
IS3 not used 0
0 0 0
OS1 additional output super-parameter [num] 0
0 0 0
OS2 additional output super-parameter [num] 0
0 0 0
FOP fans mode super-parameter [num] 131
131 131 135
DOP defrost mode super-parameter [num] 7
7 7 5
ALH upper temperature alarm limit [°C/°F] 50 50
50 50
ALL lower temperature alarm limit [°C/°F] 14 14
14 14
ALD temperature alarm delay [min] 60
60 60 60
ADS temperature alarm delay after start [min] 180
180 180 180
ADF temperature alarm delay after defrost[min] 120
120 120 120
HYH upper differential cooling action [°C/°F] 4 4
4 4
HYL lower differential cooling action [°C/°F] 0 0
0 0
MNT number of trays of blast chiller [num] 15
15 15 15
DAC compressor stop delay [sec] 3
3 3 3
ADL minimum time of stop compressor [sec] 60
60 60 60
ASS start compressor delay at power on [sec] 30
30 30 30
CON compressor on time in probe faulty [min] 5
5 5 5
COF compressor off time in probe faulty [min] 10
10 10 10
CPH not used 90
90 90 90
FAS evaporator fan set point [°C/°F] 50 50
50 50
HFF differential of fan set point [°C/°F] 9 9
9 9
FAD delay of fan start in evaporator probe faulty [sec] 5
5 5 5
FSD stop evaporator fan temperature in defrost [°C/°F] 14 14
14 14