Blast Chiller Touch Screen Manual
67
Rev08/04/2015
Parameter Description 5 PANS 115V 5 PANS 230V
SELF CONTAINED 230V
TROLLEY
MBP time range in which is performed the mains voltage control [hours] 1
1 1 1
RL1 relay 1 action type [num] 1
1 1 1
RL2 relay 2 action type [num] 13
13 13 17
RL3 relay 3 action type [num] 17
17 17 13
RL4 relay 4 action type [num] 13
13 13 13
RL5 relay 5 action type [num] 0
0 0 0
RL6 relay 6 action type [num] 11
11 11 11
RL7 relay 7 action type [num] 10
10 10 10
RL8 relay 8 action type [num] 1
1 1 1
SRV remaining time before maintenance [day] 800
800 800 800
PCA cabinet set point in prechilling [°C/°F] 28 28
28 28
PCF evaporator fan speed in prechilling [num] 10
10 10 10
PFA cabinet set point in prefreezing [°C/°F] -22 -22
-22 -22
PFF evaporator fan speed in prefreezing [num] 10
10 10 10
DWA load tolerance on relays [%] 20
20 20 20
STO max storage time without hot gas defrost [hours] 48
48 48 48
DFS
difference between core probe
and cabinet probe to detect core probe
inserted [°C/°F]
18 18
18 18
STE sterilization cycle duration [sec] 300
300 300 300
PRH heating core probe cycle duration [sec] 60
60 60 60
VOF mains voltage sensor offset [num] 77
77 77 77
PTE not used 20
20 20 20
PTI not used 12
12 12 12
MRT max recharging time of battery [hours] 20
20 20 20
FCD max first recharging time of battery [hours] 12
12 12 12
BTD max duration of battery test [sec] 3
3 3 3
TBT consecutive battery test interval time [min] 5
5 5 5
NMT not used 250
250 250 250