Instructions for the installer
FLUE OUTLET WITH SEPARATE DUCTS Ø 80 mm
It is not permitted to position the two termi-
nals on opposite walls.
-
curve with narrow radius Ø 80 =9 m
-
curve with wide radius Ø 80 = 2,5 m
-
horizontal suction terminal Ø 80 = 2,3 m
-
horizontal evacuation terminal Ø 80 = 3,5 m
-
vertical evacuation duct Ø 80 = 5,3 m
The maximum allowable length of the horizontal separate pi-
pes Ø 80 is of 64 metres.
For rectilinear length it is intended without cur-
ves and suction/ evacuation terminals.
or the calculation related to the configurations, (example
1 or 2) it is necessary to deduct, from the maximum
allowed length, the resistance in meters related to the
different accessories (see table).
00361435
KIT5770C
KIT5780C
TSC0130C
or
TSC0150C
L1
L2
L 1
L 2
L max = L1+L2 =
2 curve with wide radius
5,0 m -
61,0 m
64,0 m -
L max = L1+L2 = 64 m
Table of the flue losses for smoke accessories Ø 80 mm
For each one of them deduct, from the maximum
allowed Length, the corresponding flue losses in meters.
120
Ø 80
185 min
210 max
257 (24 kW)
242 (35 kW)
372