19
ENGLISH
Installation Instructions
3.6 - FLUE GAS EXHAUST PIPE CONNECTION
FOR BOILERS WITH FORCED DRAUGHT
To connect the ue gas exhaust pipe, local and na-
tional standards must be observed
In the event the boiler is replaced, ALWAYS re-
place the ue gas pipe as well.
The boiler is type approved for the exhaust congu-
rations listed below:
C13x C13
% Slope towards inlet = 3%
TOTAL LENGTH (LA intake + L Exhaust)
COAXIAL Ø60/100 DOUBLE Ø80
FROM [m] TO [m] FROM [m] TO [m]
NA NA 1 + 1
40
(20A+20S)
COAXIAL Ø80/125 DOUBLE Ø60
FROM [m] TO [m] FROM [m] TO [m]
1 5 NA NA
Distance between air
inlet pipe and ue gas
exhaust pipe: min 250
mm - max 500
Horizontal exhaust and intake terminals directed
outside via coaxial or double pipes..
C33x C33
TOTAL LENGTH (LA intake + L Exhaust)
COAXIAL Ø60/100 DOUBLE Ø80
FROM [m] TO [m] FROM [m] TO [m]
NA NA 0,5 + 0,5
40
(20A+20S)
COAXIAL Ø80/125 DOUBLE Ø60
FROM [m] TO [m] FROM [m] TO [m]
1 7 NA NA
ertical exhaust and intake terminals directed out-
side via coaxial or double pipes.
C53x C53
C53
NOT ALLOWED C53
TOTAL LENGTH (LA intake + L Exhaust)
DOUBLE Ø80 DOUBLE Ø60
FROM [m] TO [m] FROM [m] TOA [m]
1 + 1
40
(max 30 S)
NA NA
Separate combustion air intake and combustion
products evacuation pipes.
These pipes can discharge into areas with di󰀨erent
pressure.
C43x C43
Collective chimney ue system, consisting of two
pipes, one for combustion air intake and the other
one for combustion products evacuation, coaxial
or double.