9
Technical Features
ENGLISH
1.8 - BOILER ANTIFREEZE PROTECTION
ANTIFROST PROTECTION
Press ‘BLUE’’ button, up to led M OFF.
This protection can intervene only if the
electricity and gas supplies are connected.
If one of the two is not available and upon reset
11 (SR) a temperature between 2 ÷ 5°C is
detected, the appliance will behave as described
in tab. pos 2.
The heating system can be protected e󰀨ectively
from frost by using antifreeze products with
inhibitor for heating systems (specific for
multidmetal)
Do not use car engine antifreeze products as
they could damage the water gaskets.
P
O
S
ANTIFREEZE FUNCTION
Power supplies 11 - SR (*)
Status
antifreeze function
Actions
Electric Gas
1 ON ON < 7 °C ON - Burner and Pump ON until T > 15°C
2
ON OFF
< 5 ÷ 5 °C ON
FAULT SIGNAL CODE Fr (E16)
(with Electrical power supply ON)
(see par. 4.6 - ERROR CODES).
Ignition inhibited.
OFF ON OFF Ignition inhibited.
OFF OFF OFF Ignition inhibited.
(*) Flow sensor