ENGLISH
Installation Instructions
ATTENTION!
Function reserved for Authorised Assistance
Centres only.
The user is NOT authorised to activate the
function described below.
It is possible to adjust the maximum thermal capacity in heating
mode, by decreasing the burner pressure value.
3.12.1 - ADAPTATION OF THE POWER TO THE HEATING SYSTEM
E.g. ALKON 50 c
to decrease the output of the boiler to 35 kW, edit parameter
FH (about 72).
Es: ALKON 70 c
to decrease the output of the boiler to 50 kW, edit parameter
FH (about 76).
Power Supply (KW)
FH (%)
Act on parameter FH to achieve the value corresponding to the
desired output.