PUMP OVERRUN - ( 2 )
Continue with the modication of parameters by pressing
the - (MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM TO DEFAULT
1 min 10 min 5 min
Pump overrun time after DHW operation - ( 3 )
Continue with the modication of parameters by pressing
the - (MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM TO DEFAULT
0 sec. 60 sec. 30 sec
CAPACITY TO FLOW-RATE RATIO - ( 5 )
Continue with the modication of parameters by pressing
the - (MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM TO DEFAULT
20 100 99
DHW: ENABLE THE TEMPERATURE SENSOR - ( 7 )
Continue with the modication of parameters by pressing
the - (MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM TO DEFAULT
0 1 0
MODULATING PUMP MINIMUM MOD. LEVEL - ( 6 )
Continue with the modication of parameters by pressing
the - (MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM TO DEFAULT
ALKON 34,5 - 50 ALKON 70
0 % 99 % 19 25
RELAY PUMP BOILER COLLECTOR - ( 4 )
Continue with the modication of parameters by pressing
the - (MINUS)
Repeat the operations A-B-C to change value
VALUE
FROM TO DEFAULT
0 1 0