SPECIFICATIONS
Rating: 120V/240V AC, 60Hz
MAXIMUM LOAD: 3000W
(12.5A)
3000W @ 240V or
1500W @ 120V
MINIMUM LOAD: 500W
TROUBLESHOOTING GUIDE
Specifications:
Number of programs: 7 Day with 4 settings per day
Temperature display range: 0 – 55°C (34 – 99.5°F)
Temperature setting range: 5 – 35°C (41 – 95°F)
PROBLEM SOLUTION
LCD screen is blank.
- Check if the circuit breaker is open.
- Check if there has been a power failure.
- Check that the thermostat is wired to a 500W or greater circuit
- Check the wiring installation with a certified electrician.
- Press the RESET button under the faceplate
26
Programming Issues:
Heating is not being
activated at the
programmed times.
- Review the programming guide to ensure the programs have been entered correctly
- Check that the clock has been set to the correct time. (e.g. AM/PM reversed)
- Check if there has been a power failure.
- PROGRAM RESET: Press OPTION/COPY for 3 seconds to enter the option mode,
then press PROG for 3 seconds to clear programs settings only.
- RESET ALL: Press and hold the HOLD/DAY and the RESET button at the same time
to restore all setting to factory default.
Final Size: 5” x 3” / 12.5cm x 7.5cm