30 Remote Booster Power Supply Technical Reference Manual
Notes
CC1(S) modules must be wired and programmed on the Signature controller for proper
operation.
Any BPS trouble causes the CC1(S) supervision to report a trouble to the main control panel
when DIP switch SW2-6 is on. AC power failure is delayed for three hours.
CC1(S) wiring must be within three feet of the BPS enclosure and in conduit or mounted
within the BPS’s enclosure. If CC1(S) wiring is more than three feet from a BPS enclosure,
then a separate listed EOL relay (PAM1, 6254A-003, or 73402A) or equivalent must be used
to supervise the 200 mA AUX circuit wiring.
When configured for AC power loss reporting using the trouble relay (DIP switch SW2-6 ON),
the CT1 module supervises and reports the AC power loss to the control panel. When DIP
switch SW2-6 is OFF, the CT1 module is not required.
Figure 19: Multiple CC1(S) modules using the BPS’s sense inputs
+
+
+++
TB2
TB1
(16)
(15)
(15)
TB5
(17)
4
8
3
7
2
6
10
1
5
9
+
+
CC1(S)
4
8
3
7
2
6
10
1
5
9
+
+
CC1(S)
+
+ +
(19)
(16)
CT1
(18)
++
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security Edwards BPS6A and is the answer not in the manual?

UTC Fire and Security Edwards BPS6A Specifications

General IconGeneral
BrandUTC Fire and Security
ModelEdwards BPS6A
CategoryPower Supply
LanguageEnglish

Related product manuals