Remote Booster Power Supply Technical Reference Manual 31
Legend
(1) NAC1/AUX1
(2) NAC2/AUX2
(3) NAC3/AUX3
(4) NAC4/AUX4
(5) 200 mA AUX Continuous
(6) Sense 1 IN
(7) Sense 1 COM
(8) Sense 1 OUT
(9) Sense 2 IN
(10) Sense 2 COM
(11) Sense 2 OUT
(12) Trouble NO
(13) Trouble COM
(14) Trouble NC
(15) Notification appliance circuit (NAC)
(16) UL listed EOL 15 k
(17) EOL 47 k
(18) Data in from previous device or
Signature controller
(19) Data out to next device
Notes
CC1(S) modules must be wired and programmed on the Signature controller for proper
operation.
Any BPS trouble causes the CC1(S) supervision to report a trouble to the main control panel
when DIP switch SW2-6 is on. AC power failure is delayed for three hours.
If CC1(S) wiring is more than three feet from a BPS enclosure, then a separate listed EOL
relay (PAM1, 6254A-003, or 73402A) or equivalent must be used to supervise the 200 mA
AUX circuit wiring.
When configured for AC power loss reporting using the trouble relay (DIP switch SW2-6 ON),
the CT1 module supervises and reports the AC power.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the UTC Fire and Security Edwards BPS6A and is the answer not in the manual?

UTC Fire and Security Edwards BPS6A Specifications

General IconGeneral
BrandUTC Fire and Security
ModelEdwards BPS6A
CategoryPower Supply
LanguageEnglish

Related product manuals