EasyManuals Logo

Vacon CX User Manual

Vacon CX
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
Vacon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Page 16
VV
VV
V
aconacon
aconacon
acon
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
STOP
STOPSTOP
STOP
STOP
STOPSTOP
STOP
Group 5, Prohibit frequency parameters Group 5, Prohibit frequency parameters
Group 5, Prohibit frequency parameters Group 5, Prohibit frequency parameters
Group 5, Prohibit frequency parameters
Code Parameter Range Step Default Custom Description Page
5
. .
. .
. 1 Prohibit frequency 0f
max
0.1 Hz 0 Hz 33
range 1 low limit (1
..
..
. 2)
5
..
..
. 2 Prohibit frequency 0f
max
0.1 Hz 0 Hz 0 = Prohibit range 1 is off 33
range 1 high limit (1
..
..
. 2)
5
. .
. .
. 3 Prohibit frequency 0f
max
0.1 Hz 0 Hz 33
range 2 low limit (1
..
..
. 2)
5
..
..
. 4 Prohibit frequency 0f
max
0.1 Hz 0 Hz 0 = Prohibit range 2 is off 33
range 2 high limit (1
..
..
. 2)
5
. .
. .
. 5 Prohibit frequency 0f
max
0.1 Hz 0 Hz 33
range 3 low limit (1
..
..
. 2)
5
..
..
. 6 Prohibit frequency 0f
max
0.1 Hz 0 Hz 0 = Prohibit range 3 is off 33
range 3 high limit (1
..
..
. 2)
Group 6, Motor control parameters Group 6, Motor control parameters
Group 6, Motor control parameters Group 6, Motor control parameters
Group 6, Motor control parameters
Code Parameter Range Step Default Custom Description Page
6
. .
. .
. 1 Motor control mode 02 1 0 0 = Frequency control 33
1 = Speed control (open loop)
2 = Torque control (open loop)
6
. .
. .
. 2 Switching frequency 116 kHz 0.1 kHz 10/3.6 kHz Dependant on kW 34
6
. .
. .
. 3 Field weakening point 30500 Hz 1 Hz Param. 34
1
..
..
. 11
6
..
..
. 4 Voltage at field 15 200% 1% 100% 34
weakening point x U
nmot
6
. .
. .
. 5 U/F-curve mid 0500 Hz 0,1 Hz 0 Hz 34
point frequency
6
. .
. .
. 6 U/F-curve mid 0100% 0.01% 0 % 34
point voltage x U
nmot
6
. .
. .
. 7 Output voltage at 0100% 0.01% 0 % 34
zero frequency x U
nmot
6
. .
. .
. 8 Overvoltage controller 01 1 1 0 = Controller is not operating 35
1 = Controller is operating
6
..
..
. 9 Undervoltage controller 01 1 1 0 = Controller is not operating 35
1 = Controller is operating
Note!Note!
Note!Note!
Note!
STOP
STOPSTOP
STOP
= Parameter value can be changed only when the frequency converter is stopped.
STOP
STOPSTOP
STOP
STOP
STOPSTOP
STOP
STOP
STOPSTOP
STOP
STOP
STOPSTOP
STOP
STOP
STOPSTOP
STOP

Other manuals for Vacon CX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Vacon CX and is the answer not in the manual?

Vacon CX Specifications

General IconGeneral
BrandVacon
ModelCX
CategoryMedia Converter
LanguageEnglish

Related product manuals