acon Page 45
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application IIMulti-purpose Control Application II
Multi-purpose Control Application II
Vacon Plc Phone: +358-(0)201 2121 Fax: +358-(0)201 212 205
Service: +358-40-8371 150 E-mail: vacon@vacon.com
Par. 7. 17
UMCH7_17
Trip area
Time
Underload time counter
Underl.
No underl.
Trip/warning
par. 7. 14
Figure 6-31 Counting the under-
load time.
7. 187. 18
7. 187. 18
7. 18
Phase supervision of the supply voltagePhase supervision of the supply voltage
Phase supervision of the supply voltagePhase supervision of the supply voltage
Phase supervision of the supply voltage
0 = No action
1 = Warning
2 = Fault
By setting the parameter value to zero, the phase supervision of the supply voltage
will not cause tripping
.
7. 197. 19
7. 197. 19
7. 19
Thermistor input of IO-ExpanderThermistor input of IO-Expander
Thermistor input of IO-ExpanderThermistor input of IO-Expander
Thermistor input of IO-Expander
0 = No action
1 = Warning
2 = Fault
The thermistor connected to the thermistor input of the I/O-expander board supervises
the temperature of the motor. With parameter 7.19 the response of the frequency
converter can be programmed when the thermistor indicates overtemperature.
7. 207. 20
7. 207. 20
7. 20
Response to the fieldbus faultResponse to the fieldbus fault
Response to the fieldbus faultResponse to the fieldbus fault
Response to the fieldbus fault
0 = No response
1 = Warning message
2 = Fault message, stop mode after fault according to parameter 4.7
A warning or a fault action and message is generated from the fieldbus card if the
error occurs of the bus system physical layer.
8. 18. 1
8. 18. 1
8. 1
Automatic restart: number of triesAutomatic restart: number of tries
Automatic restart: number of triesAutomatic restart: number of tries
Automatic restart: number of tries
8. 28. 2
8. 28. 2
8. 2
Automatic restart: trial timeAutomatic restart: trial time
Automatic restart: trial timeAutomatic restart: trial time
Automatic restart: trial time
The Automatic restart function restarts the frequency converter after the faults selected
with parameters 8
..
..
. 48
..
..
. 8. The Start function for Automatic restart is selected with
parameter 8
. .
. .
. 3.