Table 59: Analogue input 4 (Control keypad: Menu M2 -> G2.2.5)
Index Parameter Min Max Unit Default Cust ID Description
P2.2.5.1
**
AI4 signal selec-
tion
0.1 E.10 0.1 152
TTF programming.
See Chapter 8.9
"Terminal to func-
tion" (TTF) pro-
gramming principle.
P2.2.5.2 AI4 filter time 0.00 320.00 s 0.00 153 0 = No filtering
P2.2.5.3 AI4 signal range 0 3 1 154
0 = 0-10 V
(0-20mA*)
1 = 2-10 V (4-20
mA*)
2 = -10V...+10 V*
3 = Custom range
*
P2.2.5.4
AI4 custom mini-
mum setting
-160.00 160.00 % 20.00 155
% of input signal
range. e.g. 2 mA =
10 %
P2.2.5.5
AI4 custom maxi-
mum setting
-160.00 160.00 % 100.00 156
e.g. 18 mA = 90 %
P2.2.5.6
AI4 signal inver-
sion
0 1 0 162
0 = Not inverted
1 = Inverted
*= Remember to place jumpers of block X2 accordingly. See the product's User Manual.
** = Apply the Terminal to Function method (TTF) to these parameters (see Chapter 8.9
"Terminal to function" (TTF) programming principle)
MULTI-PURPOSE CONTROL APPLICATION VACON · 151
24-HOUR SUPPORT +358 (0)201 212 575 · EMAIL: VACON@VACON.COM
6