VAF instruments 667 - 6.11 MODBUS OUTPUT TO EXTERNAL SYSTEM

Default Icon
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
COM-port settings for reading out the J3 Modbus signal at SPU3
Communication protocol
Modbus RTU
Serial interface
RS485 (2-wire)
Baud rate
57600
Data bits
8
Parity
None
Stop bits
1
Flow control
None
Function code
3 (Holding registers)
Modbus slave address
1
Modbus address list
To receive a full list containing the available standard SPU3 Modbus addresses (ASL-668
SPU3 Modbus registers list) or in case your AMS system is programmed for 16 or 32 bit
integer input signals, please contact VAF Instruments for additional information.
In case more than one (1) SPU3 is connected in the same MODBUS-loop, the slave
addresses of these SPU3’s are factory set resp. slave-1”, slave-“2”, etc.