38 Installation instructions VRT 360f
Display Set by turning the dial
Set-back temperature
Factory setting: 15 °C
Setting range: 5 ... 30° C
Set hot water temperature
Factory setting: 60 °C
Setting range 35 ... 70 °C
Correction of current room
temperature
Adjustment of the displayed
value by up to max.
+/- 3 °C
Factory setting: 0 °C
Display Set by turning the dial
Anti-legionella function
1 = Activate the anti-
legionnaire's disease
programme.
Every Wednesday, one hour
before the first time window,
a connected hot water
cylinder is heated to 70 °C,
and the circulation pump is
switched on and operated
at 70 °C for at least 30
minutes.
Factory setting: 0 (off)
11 Start-up