39GBInstallation instructions VRT 360f
Display Set by turning the dial
Two-point/analogue
operation
2-point/analogue mode
change-over.
The room temperature
thermostat is set in the
factory as a 2-point
regulation system (set
value 0). You can set it to
analogue mode by changing
the parameter to 1.
Display Set by turning the dial
Control characteristics/
route adjustment
For optimum adaptation to
the room size or radiator
configuration
Factory setting: 0
Setting range: -5 ... +5
(Positive values: slow
reaction speed of the room
temperature thermostat;
negative values:
faster reaction speed of
the room temperature
thermostat)
Start-up 11