Calibrating Sensors
For calibrating the sensors with the AWS Client software, use the 
Calibration window shown in Figure 36 on page 70. The window 
shows a list of measurements available for calibration.
CAUTION
Improper changes to sensor calibration may cause the system to 
malfunction. Changing the values requires a profound knowledge of 
calibrating sensors.
CAUTION
When you upgrade a previous QML logger software version to 3.06 or 
above, the following sensors will not operate correctly in the Sensor 
Calibration tab until they are removed from the setup and then re-
created: CM6B, CM11, QMS101, QMS102, and QMN101.
NOTE
There are two ways to calibrate a sensor with AWS Client: either via 
the graphical or the command line interface. While the command line 
option is available for all sensors, the graphical user interface is limited 
to the following sensors: wind sensor WMS302, solar radiation 
sensors CM6B/CM11 (older models), CMP6/CMP11 (current models 
with enhanced sensitivity), QMS101, QMS102, QMN101, and LI200. 
NOTE
You must load an appropriate setup to the QML logger before you are 
able to use the Calibration window.
NOTE
The Calibration window has no content for setups made with QML 
logger software versions prior to 3.06. With old setups, sensors need 
to be calibrated through the terminal connection with the appropriate 
calibration commands.