No. 416
PST error: Total timeout, position
Description
The operational position was not reached after the partial stroke
Trouble shooting
This error can be caused by:
No supply pressure
The valve is stuck
The valve is moving slow
The solenoid valve cannot be activated
It can be solved by:
Resolve the mechanical problem
Increase PST total timeout