PST error: Total timeout, pressure
Description
The pressure did not reach the start pressure after the partial stroke
Trouble shooting
This error can be caused by:
Low supply pressure
It can be solved by:
Increase pressure
Resolve the mechanical problem
Increase PST total timeout
No. 418
PST error: At 0% position
Description
The position measured to be 0%
Trouble shooting
This error can be caused by:
Position sensor was disconnected
Position sensor is operating in the illegal area
Wrong configuration of the position switches
The valve moved to 0%
It can be solved by:
Check the position sensor
Make sure the position sensor is operating within the legal area
Check the function of the position switches
Decrease the PST travel
No. 419
PST error: Wrong Switch. SP
Description
The SP switch was activated before the 100% switch was released
Trouble shooting
This error can be caused by:
Wrong configuration of the position switches

Other manuals for Val Controls IDC24-F

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Val Controls IDC24-F and is the answer not in the manual?

Val Controls IDC24-F Specifications

General IconGeneral
BrandVal Controls
ModelIDC24-F
CategoryController
LanguageEnglish

Related product manuals