9
3-2-1. DIP(Function) switch:
::
:
3-2-1-1 Output Voltage switch Function (S1,S2):
::
:Default : 120VAC
Output Voltage S1 S2
100V OFF OFF
110V ON OFF
115V OFF ON
120V ON ON
Table 5
:
Output voltage function definition
3-2-1-2 Output Frequency switch Function (S3):
::
:Default : 60HZ
Frequency S3
50HZ OFF
60HZ ON
Table 6
:
Output frequency function definition
3-2-1-3 AC Input Current Limit Select (S4,S5,S6):
::
:Default : 15A
AC Input Current
100~120V
S4 S5 S6
3A OFF OFF OFF
6A ON OFF OFF
9A OFF ON OFF
12A ON ON OFF
15A OFF OFF ON
20A ON OFF ON
25A OFF ON ON
30A ON ON ON
Table 7
:
LSC12-20000 Input current limit select function definition
3-2-1-4 Battery Type Select Function(S7,S8):
::
:Default : Flooded
Table 8
:
Battery types select function definition
Battery Type S7 S8
LiFePO4 OFF OFF
Flooded ON OFF
AGM OFF ON