4 Vac System Testing - TLS-350/350R Consoles Running a Manual Test
4-6
Figure 4-4.- TLS Console Vac Sensor Manual Test
sensors\vacsensor\fig21.eps
P
E
S
s X: (Vac Sensor Label)
TYPE: VAC SENSOR
START MANUAL TEST
PRESS <ENTER>
E
SELECT VAC SENSOR
ALL VAC SENSORS
SELECT VAC SENSOR
sX (Vac Sensor Label)
E
S
S
S
START MANUAL TEST: ALL
PRESS <ENTER>
START MANUAL TEST: sX
PRESS <ENTER>
ALL: MANUAL TEST STARTED
PRESS <STEP> TO CONTINUE
E
E
sX: MANUAL TEST STARTED
PRESS <STEP> TO CONTINUE
STOP MANUAL TEST
PRESS <ENTER>
E
C
VAC SENSOR MANUAL TEST
PRESS <ENTER>
COMM DATA
PRESS <PRINT>
VAC SENSOR EVAC HOLD
PRESS <ENTER>
S
S
S
SMARTSENSOR DIAGNOSTIC
MMM DD, YYYY HH:MM XM
SX: (Vac Sensor Label)
VAC SENSOR
SERIAL NUMBER XXXXXXXX
COMPENSATED PRESSURE:
-0.155 PSI
UNCOMPENSATED PRESSURE:
-0.094 PSI
EVACUATION STATE:
NO VACUUM
FLUID STATUS: NORMAL
VCV: CLOSED
MM-DD-YYYY HH:MM XM
LEAK RATE: 0.123 GPH
TIME TO NO VAC:
100:00 HHH:MM
MM-DD-YYYY HH:MM XM
EVAC RATIO:5.2 @-4.1PSI
SENSOR FAULTS:
NONE
T
Go to Figure on next page.
TO SELECT INDIVIDUAL VAC SENSORSTO SELECT ALL VAC SENSORS
SELECT VAC SENSOR
ALL VAC SENSORS
SELECT VAC SENSOR
sX (Vac Sensor Label)
STOP MANUAL TEST: ALL
PRESS <ENTER>
STOP MANUAL TEST: sX
PRESS <ENTER>
ALL: MANUAL TEST ABORTED
PRESS <STEP> TO CONTINUE
sX: MANUAL TEST ABORTED
PRESS <STEP> TO CONTINUE
TO SELECT INDIVIDUAL VAC SENSORSTO SELECT ALL VAC SENSORS
S
Rate in gph at which air is entering the interstitial
space. A Vac Warning may be posted if this
rate is >22.4 gph.
Vacuum control valve (in Vac Sensor)
Liquid float (in Vac Float)
Pressure sensor value minus ATM P sensor value
Measured by pressure sensor (in Vac Sensor)
Predicted time (in hours : minutes) it would take for
the interstitial pressure to equal -1 psi. A Vac Warning
Alarm will be posted if this rate is <8 hours.
A Evac Ratio >1.0 is required or evacuation will abort.
Pressure value (-4.1) is the pressure recorded
at the time this ratio was calculated.
s X: (Vac Sensor Label)
SERIAL NUMBER XXXXXXXXX
S
VAC SENSOR DIAGS
PRESS <ENTER>
M
P
E
Enter Mode
C
Change
F
Function Print
S
Step
T
Tank/Sensor
Repress for
next Tank/Sensor
Key Legend
SMART SENSOR DIAGNOSTIC
PRESS <STEP> TO CONTINUE
DIAG MODE
PRESS <FUNCTION> TO CONT
F
s X: (Label)
TYPE: XXX SENSOR
S
See example
printout at
right.
C
S
E
E
E
E
E
E
CONSTANTS
PRESS <PRINT>
CHANNELS
PRESS <PRINT>
S
S
S
SMART SENSOR INSTALL LOG
PRESS <PRINT>
S

Table of Contents

Other manuals for Veeder-Root TLS-350

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Veeder-Root TLS-350 and is the answer not in the manual?

Veeder-Root TLS-350 Specifications

General IconGeneral
BrandVeeder-Root
ModelTLS-350
CategoryAccessories
LanguageEnglish

Related product manuals