24 Capacitive electrodes EL 4 … 20 mA - compact
Electrical connection
A
B
2
1
E2
E1
A2
A1
2
1
A2
A1
E2
E1
Vessel with cathodic corrosion protection
(Ex)-area Zone 1
Not (Ex)-area
overvoltage
protection unit
mounted on
oscillator
Oscillator
b)Capacitive electrodes with external overvoltage
protection unit
Screen
Cathodic tank protection
2 … 24 V (object voltage)
CB
2-36
CAP
E32(H)EX
External earth terminal
Internal earth terminal
Vessel
Zone 0
Li, Ci of the oscillator with
overvoltage protection unit
Li = 0,27 mH
Ci = 8,5 nF
Control room
either: Overvoltage
protection insert
Signal
cond.
instr.
or
safety
barrier
Type B62-36G
Li=0,15 mH
Ci=2,5 nF
Overvoltage protection insert
Overvoltage protection
instrument in metal
housing or plastic
housing. The metal
housing must be
mounted earth free
External earth terminal
Internal earth terminal
Cathodic tank protection
2 … 24 V (object voltage)
Isolated line
min. 4 mm
2
Vessel
Zone 0
Oscillator
Li=0,12 mH
Ci=6 nF
Screen
CAP
E32
(H)Ex
Type
B62-36G
Li=0,15 mH
Ci=2,5 nF
Between control room and overvoltage protection
system a suitable cable must be used, if
necessary with metal cover or screen. Metal
cover or screen - if necessary - must be only
connected to the overvoltage protection system
on the electrode side. The cable must have an
outer isolation. Test voltage of the cable A: 500
V AC
Between overvoltage protection system and
capacitive electrode a suitable cable with metal
cover, screen or a suitable cable with metal
protection tube must be used (metal cover or
protection tube must not be earthed).
Test voltage of the cable B: 1500 V AC
a) Capacitive electrodes with integral overvoltage
protection unit type CB 2-36
A
B