IP address
Fix IP address
LAN/Internet
IP address:
192.168.200.200
Subnet mask:
255.255.255.0
Change?
à Enter the values via the appropriate keys and save your settings
with [OK]. Disconnect briey the operating voltage so that the
modied settings become eective.
Date and time can be entered in this menu item for instruments with
integrated RS232/Ethernet interface. These time settings are buered
in case of power failure for approx. 3 days.
Time/Date
8:40
28.09.2004
à Enter the values via the appropriate keys and save your settings
with [OK].
VEGAMET 624 can process measured values from 4 20 mA/HART
sensors via analogue communication as well as via digital HART
protocol.
Analogue 4 20 mA transmission
In the standard setting of VEGAMET 624 the measured value
transmission is carried out via analogue 4 20 signal. An adjustment
in the sensor inuences directly the input variable of VEGAMET 624.
Only carry out the adjustment on one instrument, either on VEGAMET
624 or on the sensor. The adjustment in VEGAMET 624 is a lways
carried out in mA (analogue transmission).
Digital HART transmission
For transmission via HART, VEGAMET 624 must be informed which
sensor value should be used for further processing. Depending on the
sensor type, this can be distance, pressure or temperature. With all
VEGA HART sensors, always the unchanged initial value of the sensor
is transmitted to VEGAMET 624. Thus, the adjustment must always
carried out on VEGAMET 624, never on the sensor. Dierent
parameters and meas. units are available.
Device settings - Time/
Date
Measurement loop - In-
put
VEGAMET 624 4 20 mA/HART signal conditioning instrument 19
6 Setup with the integrated indicating and adjustment unit
28969-EN-091116